LC1D25B7TQ

CONT 25A 24V50/60Hz

Trade Price

£87.56

Per

1

Unit

EA

Pack Quantity

24

LC1D25B7TQ

Information

TeSys D contactor, 3 poles (3NO), for motor control applications up to 25A/690V AC-3/3e (4kW@400V). It provides a 24V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Pack of 10 units. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys TeSys Deca

Range of product

TeSys Deca

Product or component type

Contactor

Device short name

LC1D

contactor application

Resistive load Motor control

utilisation category

AC-3 AC-1 AC-3e

Poles description

3P

[Ue] rated operational voltage

Power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current

25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 25 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

[Uc] control circuit voltage

24 V AC 50/60 Hz

Motor power kW

11 kW at 380...400 V AC 50/60 Hz (AC-3) 15 kW at 500 V AC 50/60 Hz (AC-3) 15 kW at 660...690 V AC 50/60 Hz (AC-3) 5.5 kW at 220...230 V AC 50/60 Hz (AC-3) 11 kW at 415...440 V AC 50/60 Hz (AC-3) 5.5 kW at 400 V AC 50/60 Hz (AC-4) 11 kW at 380...400 V AC 50/60 Hz (AC-3e) 15 kW at 500 V AC 50/60 Hz (AC-3e) 15 kW at 660...690 V AC 50/60 Hz (AC-3e) 5.5 kW at 220...230 V AC 50/60 Hz (AC-3e) 11 kW at 415...440 V AC 50/60 Hz (AC-3e)

Motor power hp

5 hp at 200/208 V AC 50/60 Hz for 3 phases motors conforming to CSA 5 hp at 200/208 V AC 50/60 Hz for 3 phases motors conforming to UL 3 hp at 230...240 V AC 50/60 Hz for 1 phase motors conforming to CSA 3 hp at 230...240 V AC 50/60 Hz for 1 phase motors conforming to UL 15 hp at 460/480 V AC 50/60 Hz for 3 phases motors conforming to CSA 15 hp at 460/480 V AC 50/60 Hz for 3 phases motors conforming to UL 2 hp at 115 V AC 50/60 Hz for 1 phase motors conforming to CSA 2 hp at 115 V AC 50/60 Hz for 1 phase motors conforming to UL 20 hp at 575/600 V AC 50/60 Hz for 3 phases motors conforming to CSA 20 hp at 575/600 V AC 50/60 Hz for 3 phases motors conforming to UL 7.5 hp at 230...240 V AC 50/60 Hz for 3 phases motors conforming to CSA 7.5 hp at 230...240 V AC 50/60 Hz for 3 phases motors conforming to UL

Compatibility code

LC1D

Pole contact composition

3 NO

Protective cover

With

[Ith] conventional free air thermal current

10 A (at 60 °C) for control circuit 40 A (at 60 °C) for power circuit

Irms rated making capacity

140 A AC for control circuit conforming to IEC 60947-5-1 450 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity

450 kA at 440 V for power circuit conforming to IEC 60947

Associated fuse rating

10 A gG for control circuit conforming to IEC 60947-5-1 40 A at <= 690 V coordination type 2 for power circuit 63 A at <= 690 V coordination type 1 for power circuit

Average impedance

2 mOhm - Ith 40 A 50 Hz for power circuit

Power dissipation per pole

3.2 W AC-1 1.25 W AC-3 1.25 W AC-3e

[Ui] rated insulation voltage

Control circuit: 600 V CSA certified Control circuit: 600 V UL certified Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Control circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 690 V conforming to IEC 60947-4-1

Overvoltage category

III

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability

15000000 cycles

Control circuit type

AC at 50/60 Hz

Coil technology

Without built-in bidirectional peak limiting diode suppressor

Control circuit voltage limits

0.3...0.6 Uc (60 °C):drop-out AC 50/60 Hz 0.8...1.1 Uc (60 °C):operational AC 50 Hz 0.85...1.1 Uc (60 °C):operational AC 60 Hz

Inrush power in VA

70 VA cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA

7 VA 50/60 Hz cos phi 0.3 (at 20 °C)

Heat dissipation

2…3 W at 50/60 Hz for control circuit

Operating time

4...19 ms opening 12...22 ms closing

Maximum operating rate

3600 cyc/h 60 °C

Connections - terminals

Control circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminal 2 1…2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminal 1 1.5…10 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminal 2 2.5…10 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminal 1 2.5…10 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminal 2 2.5…10 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminal 1 1…10 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminal 2 1.5…6 mm² - cable stiffness: flexible with cable end

Tightening torque

Control circuit: 1.7 N.m - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - with screwdriver Philips No 2 Power circuit: 2.5 N.m - with screwdriver flat Ø 6 mm Power circuit: 2.5 N.m - with screwdriver Philips No 2 Control circuit: 1.7 N.m - with screwdriver pozidriv No 2 Power circuit: 2.5 N.m - with screwdriver pozidriv No 2

Auxiliary contact composition

1 NO + 1 NC

Minimum switching voltage

17 V for control circuit

Minimum switching current

5 mA for control circuit

Insulation resistance

> 10 MOhm for control circuit

Non-overlap time

1.5 ms on de-energisation between NC and NO contacts 1.5 ms on energisation between NC and NO contacts

mounting support

Rail Plate

Standards

UL 508 EN/IEC 60947-5-1 CSA C22.2 No 14 EN/IEC 60947-4-1 IEC 60335-1

product certifications

BV GL LROS (Lloyds register of shipping) UL DNV CSA RINA GOST CCC UKCA

IP degree of protection

IP2X conforming to IEC 60529 IP2X conforming to VDE 0106

Climatic withstand

conforming to IACS E10 exposure to damp heat conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Permissible ambient air temperature around the device

-5…60 °C -40…70 °C at Uc

Operating altitude

3000 m without derating

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

Shocks contactor closed (15 Gn for 11 ms) Shocks contactor opened (8 Gn for 11 ms) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz)

height

85 mm

Width

45 mm

Depth

92 mm

Net weight

3.7 kg

Quantity per set

Set of 10

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

15 cm

Package 1 Width

30 cm

Package 1 Length

40 cm

Package 1 Weight

402 g

Unit Type of Package 2

S02

Number of Units in Package 2

24

Package 2 Height

15 cm

Package 2 Width

30 cm

Package 2 Length

40 cm

Package 2 Weight

10.103 kg

Warranty

18 months

Document Links