Trade Price
£36.66
Per
1
Unit
EA
Pack Quantity
1
Range
TeSys
Product name
TeSys CAK
Product or component type
Control relay
Device short name
CA2K
contactor application
Control circuit
utilisation category
AC-15
control circuit type
AC
Coil type
Standard
Coil technology
Without integral suppression device
Pole contact composition
2 NO + 2 NC
[Uc] control circuit voltage
480 V AC 50/60 Hz
Connections - terminals
1 x 0.34…1.5 mm²flexible with cable end 1 x 0.34…2.5 mm²flexible with cable end 1 x 0.75 mm²flexible without cable end 1 x 1.5 mm²solid 2 x 4 mm²flexible without cable end 2 x 4 mm²solid
Control circuit voltage limits
Drop-out: <= 0.2 Uc at 50/60 Hz (at <50 °C) Operational: 0.8...1.15 Uc at 50/60 Hz (at <50 °C)
[Ui] rated insulation voltage
690 V - conforming to BS 5424 690 V - conforming to IEC 60947 750 V - conforming to VDE 0110 group C 600 V - conforming to CSA C22.2 No 14
Flame retardance
Class C2 conforming to NF F 16-101 Class C2 conforming to NF F 16-102 V1 conforming to UL 94
Tightening torque
0.8…1.3 N.m - on screw clamp terminals - cable 1.5…4 mm² - with screwdriver Philips M6
[Ue] rated operational voltage
<= 690 V AC <= 400 Hz
[Ith] conventional free air thermal current
10 A (at 50 °C)
Associated fuse rating
10 A gG at <= 690 V conforming to IEC 60947 10 A gG at <= 690 V conforming to VDE 0660
Inrush power in VA
30 VA (at 20 °C)
Hold-in power consumption in VA
4.5 VA (at 20 °C)
Mechanical durability
10000000 cycles
Maximum operating rate
10000 cyc/h 20 °C
Operating time
10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing 15...25 ms coil de-energisation and NC closing 5...15 ms coil energisation and NC opening
Minimum switching current
5 mA
Minimum switching voltage
17 V
Non-overlap time
1.5 ms on de-energisation between NC and NO contacts 1.5 ms on energisation between NC and NO contacts
Non overlap distance
0.5 m
Insulation resistance
> 10 MOhm
height
58 mm
Width
45 mm
Depth
57 mm
Net weight
0.18 kg
standards
VDE 0660 NF C 63-140 IEC 60947 BS 5424
product certifications
UL CSA UKCA
IP degree of protection
IP2X conforming to VDE 0106
Protective treatment
TC conforming to IEC 60068
Ambient air temperature for operation
-25…50 °C
Ambient air temperature for storage
-50…80 °C
Operating altitude
2000 m without derating
Shock resistance
10 gn control relay open 15 gn control relay closed
Vibration resistance
2 gn 5…300 Hz control relay open 4 gn 5…300 Hz control relay closed
Heat dissipation
1.3 W at 50/60 Hz
Immunity to microbreaks
2 ms
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
6.6 cm
Package 1 Width
4.8 cm
Package 1 Length
6.2 cm
Package 1 Weight
180.0 g
Warranty
18 months