LC1D65008M5

CONT 80A4PL 2NO+2NC220V50Hz

Trade Price

£405.83

Per

1

Unit

EA

Pack Quantity

1

LC1D65008M5

Technical Specifications

Range

TeSys

Range of product

TeSys Deca

Product or component type

Contactor

Device short name

LC1D

contactor application

Resistive load

utilisation category

AC-1

Poles description

4P

[Ue] rated operational voltage

Power circuit: <= 690 V AC 25...400 Hz Power circuit: <= 300 V DC

[Ie] rated operational current

80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

[Uc] control circuit voltage

220 V AC 50 Hz

Compatibility code

LC1D

Pole contact composition

2 NO + 2 NC

Contact compatibility

M1

Protective cover

Without

[Ith] conventional free air thermal current

80 A (at 60 °C) for power circuit

Irms rated making capacity

1000 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity

1000 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current

520 A 40 °C - 10 s for power circuit 900 A 40 °C - 1 s for power circuit 110 A 40 °C - 10 min for power circuit 260 A 40 °C - 1 min for power circuit

Associated fuse rating

125 A gG at <= 690 V coordination type 1 for power circuit 125 A gG at <= 690 V coordination type 2 for power circuit

Average impedance

1.5 mOhm - Ith 80 A 50 Hz for power circuit

Power dissipation per pole

9.6 W AC-1

[Ui] rated insulation voltage

Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Power circuit: 690 V conforming to IEC 60947-4-1

Overvoltage category

III

Pollution degree

3

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability

6 Mcycles

Electrical durability

1.4 Mcycles 80 A AC-1 at Ue <= 440 V

Control circuit type

AC at 50 Hz

Coil technology

Without built-in suppressor module

Control circuit voltage limits

0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz 0.3...0.6 Uc (-40…70 °C):drop-out AC 50 Hz 1...1.1 Uc (60…70 °C):operational AC 50 Hz

Inrush power in VA

160 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA

15 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation

4…5 W at 50 Hz

Operating time

4...19 ms opening 12...26 ms closing

Maximum operating rate

3600 cyc/h 60 °C

Connections - terminals

Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1…35 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 1…25 mm² - cable stiffness: solid without cable end

Tightening torque

Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

mounting support

Plate Rail

Standards

CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508

product certifications

CSA CCC RINA LROS (Lloyds register of shipping) GL UL DNV GOST BV

IP degree of protection

IP20 front face conforming to IEC 60529

Protective treatment

TH conforming to IEC 60068-2-30

Climatic withstand

conforming to IACS E10 exposure to damp heat

Permissible ambient air temperature around the device

-40…60 °C 60…70 °C with derating

Operating altitude

0...3000 m

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

Shocks contactor open (8 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz)

height

127 mm

Width

85 mm

Depth

125 mm

Net weight

1.45 kg

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

11.2 cm

Package 1 Width

13.5 cm

Package 1 Length

15.5 cm

Package 1 Weight

1.471 kg

Unit Type of Package 2

S02

Number of Units in Package 2

5

Package 2 Height

15 cm

Package 2 Width

30 cm

Package 2 Length

40 cm

Package 2 Weight

7.593 kg

Warranty

18 months

Document Links

Datasheet