GV4AS137

Shunt Trip 110-130V AC/DC

Trade Price

£78.38

Per

1

Unit

EA

Pack Quantity

1

GV4AS137

Information

TeSys GV electrical trip unit, MX shunt trip, 110-130V AC 50Hz/60Hz or 125V DC, for motor circuit breakers GV4. It trips the circuit breaker when the control voltage is applied in limits 0.7-1.1 Uc with an impulse duration greater than 20ms or a maintained signal. To be plugged inside the circuit breaker, connection by spring terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys

Device short name

MX

Product or component type

Voltage release

Device application

Control

Range compatibility

TeSys (TeSys GV4) TeSys (TeSys BV4)

Voltage release type

Shunt trip release

[Uc] control circuit voltage

110...130 V AC 50/60 Hz 125 V DC

[Ui] rated insulation voltage

130 V conforming to IEC 60947-1

Threshold tripping voltage

0.7...1.1 Un failsafe opening < 0.7 Un possible opening

impulse duration

>= 20 ms

Mounting mode

Internal mounting

Maximum inrush power in VA

6 VA

Maximum inrush power in W

4 W

Maximum hold-in power consumption in VA

10 VA

Maximum hold-in power consumption in W

1 W

Mechanical durability

20000 cycles

Operating time

< 50 ms

Connections - terminals

Spring terminals 1 0.5…1.5 mm² - cable stiffness: flexible without cable end

wire stripping length

8 mm

Quantity per set

Set of 1

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

3.500 cm

Package 1 Width

6.000 cm

Package 1 Length

8.500 cm

Package 1 Weight

64.000 g

Unit Type of Package 2

BB1

Number of Units in Package 2

10

Package 2 Height

9.000 cm

Package 2 Width

13.000 cm

Package 2 Length

18.500 cm

Package 2 Weight

696.000 g

Unit Type of Package 3

S03

Number of Units in Package 3

10

Package 3 Height

30.000 cm

Package 3 Width

30.000 cm

Package 3 Length

40.000 cm

Package 3 Weight

1.120 kg

Warranty

18 months

Document Links

Datasheet