LC1D40004M7S335

CONT 4P AC1 440V 60A COIL

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

LC1D40004M7S335

Technical Specifications

Range

TeSys

Range of product

TeSys Deca

Product or component type

Contactor

Device short name

LC1D

contactor application

Resistive load

utilisation category

AC-1 AC-3 AC-3e AC-4

Poles description

4P

[Ue] rated operational voltage

Power circuit: <= 1000 V AC 25...400 Hz

[Ie] rated operational current

60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

[Uc] control circuit voltage

220 V AC 50/60 Hz

Compatibility code

LC1D

Pole contact composition

4 NO

Contact compatibility

M1

Protective cover

With

[Ith] conventional free air thermal current

60 A (at 60 °C) for power circuit

Irms rated making capacity

800 A at 440 V AC for power circuit conforming to IEC 60947

Rated breaking capacity

800 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current

72 A 40 °C - 10 min for power circuit 165 A 40 °C - 1 min for power circuit 320 A 40 °C - 10 s for power circuit 720 A 40 °C - 1 s for power circuit

Associated fuse rating

80 A gG at <= 690 V coordination type 1 for power circuit 80 A gG at <= 690 V coordination type 2 for power circuit

Average impedance

1.5 mOhm - Ith 60 A 50 Hz for power circuit

Power dissipation per pole

5.4 W AC-1

[Ui] rated insulation voltage

Power circuit: 1000 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified

Overvoltage category

III

Pollution degree

3

[Uimp] rated impulse withstand voltage

8 kV conforming to IEC 60947

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability

6 Mcycles

Electrical durability

1.4 Mcycles 60 A AC-1 at Ue <= 440 V

Control circuit type

AC at 50/60 Hz

Coil technology

Without built-in suppressor module

Control circuit voltage limits

0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz

Inrush power in VA

245 VA 50/60 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA

26 VA 50/60 Hz cos phi 0.3 (at 20 °C)

Heat dissipation

6…10 W at 50/60 Hz

Operating time

4...19 ms opening 12...26 ms closing

Maximum operating rate

3600 cyc/h 60 °C

Connections - terminals

Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: flexible without cable end

Tightening torque

Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 to Ø 8 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Auxiliary contact composition

Without

mounting support

Plate Rail

Standards

EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 EN 60335-1

product certifications

IEC UL CSA CCC UKCA

IP degree of protection

IP20 front face conforming to IEC 60529

Climatic withstand

conforming to IACS E10 exposure to damp heat conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Permissible ambient air temperature around the device

-40…60 °C 60…70 °C with derating

Operating altitude

0...3000 m

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V0 conforming to UL 94

Mechanical robustness

Shocks contactor open (8 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz)

height

127 mm

Width

85 mm

Depth

130 mm

Net weight

1.44 kg

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

14.8 cm

Package 1 Width

13.1 cm

Package 1 Length

10.8 cm

Package 1 Weight

2.5 kg

Warranty

18 months

Document Links

Datasheet