Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1
This contact block allows fast and easy replacement and configuration of your push buttons and selector switches It protects operators from unexpected contact with live circuits thanks to its IP20 protection index It is easily installed and replaced on XACM and XACB pendant control stations and connects to control circuits with simple screw-clamp connections
Range of product
Harmony XAC
Product or component type
Contact block
Component name
XENB
Electrical circuit type
Control circuit
Contact block application
2-speed
Contact block type
Single
Type of operator
Spring return
Product compatibility
XACB XACM
Mechanical interlocking
Without mechanical interlock
Contacts type and composition
2 NO
Mounting of block
Front mounting
contact operation
Staggered Slow-break
Connections - terminals
Screw clamp terminals, 1 x 2.5 mm² with or without cable end Screw clamp terminals, 2 x 1.5 mm² with or without cable end
Mechanical durability
1000000 cycles
Contact code designation
A300 AC-15, Ue = 240 V, Ie = 3 A conforming to IEC 60947-5-1 appendix A Q300 DC-13, Ue = 250 V, Ie = 0.27 A conforming to IEC 60947-5-1 appendix A
[Ithe] conventional enclosed thermal current
10 A
[Ui] rated insulation voltage
400 V (pollution degree 3) conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-1
Maximum resistance across terminals
25 MOhm
Short-circuit protection
10 A fuse protection by cartridge fuse type gG
Rated operational power in W
31 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 48 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C 35 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 120 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C 48 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 24 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
Rated operational power in VA
140 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 24 V 50/60 Hz, load factor = 0.5 (inductive load) 210 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 48 V 50/60 Hz, load factor = 0.5 (inductive load) 640 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 127 V 50/60 Hz, load factor = 0.5 (inductive load) 680 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 230 V 50/60 Hz, load factor = 0.5 (inductive load)
Terminals description ISO n°1
(33-34)NO (43-44)NO_CL
Terminal identifier
(13-14)NO (11-12)NC
Net weight
0.05 kg
standards
IEC 60947-5-1 CSA C22.2 No 14 IEC 60947-5-1
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…70 °C
Vibration resistance
15 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
Shock resistance
100 gn conforming to IEC 60068-2-27
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
3.4 cm
Package 1 Width
9.7 cm
Package 1 Length
7.5 cm
Package 1 Weight
46.0 g
Unit Type of Package 2
S02
Number of Units in Package 2
25
Package 2 Height
15.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
1.499 kg
Warranty
18 months