LC1G265LSEA

Cont G265 3P Adv 200-500V ACDC

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

LC1G265LSEA

Information

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 265A 160kW@440V. It provides a 200-500V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 290mm x 140mm x 209mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.

Technical Specifications

Range

TeSys

Range of product

TeSys Giga

Product or component type

Contactor

Device short name

LC1G

contactor application

Power switching Motor control

utilisation category

AC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8b AC-8a DC-1 DC-3 DC-5

Poles description

3P

[Ue] rated operational voltage

<= 1000 V AC 50/60 Hz <= 460 V DC

[Ie] rated operational current

385 A (at <40 °C) at <= 1000 V AC-1 265 A (at <60 °C) at <= 400 V AC-3

[Uc] control circuit voltage

200...500 V AC 50/60 Hz 200...500 V DC

Control circuit voltage limits

Operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)

[Uimp] rated impulse withstand voltage

8 kV

Overvoltage category

III

Rated breaking capacity

2380 A at 440 V

[Icw] rated short-time withstand current

2.2 kA - 10 s 1.23 kA - 30 s 0.95 kA - 1 min 0.62 kA - 3 min 0.48 kA - 10 min

Associated fuse rating

315 A aM at <= 440 V for motor 250 A aM at <= 690 V for motor 400 A gG at <= 690 V

Average impedance

0.000144 Ohm

[Ui] rated insulation voltage

1000 V

Power dissipation per pole

20 W AC-1 - Ith 385 A 11 W AC-3 - Ith 265 A

Compatibility code

LC1G

Pole contact composition

3 NO

Auxiliary contact composition

1 NO + 1 NC

Motor power kW

75 kW at 230 V AC 50/60 Hz (AC-3e) 132 kW at 400 V AC 50/60 Hz (AC-3e) 132 kW at 415 V AC 50/60 Hz (AC-3e) 160 kW at 440 V AC 50/60 Hz (AC-3e) 160 kW at 500 V AC 50/60 Hz (AC-3e) 200 kW at 690 V AC 50/60 Hz (AC-3e) 160 kW at 1000 V AC 50/60 Hz (AC-3e) 75 kW at 230 V AC 50/60 Hz (AC-3) 132 kW at 400 V AC 50/60 Hz (AC-3) 132 kW at 415 V AC 50/60 Hz (AC-3) 160 kW at 440 V AC 50/60 Hz (AC-3) 160 kW at 500 V AC 50/60 Hz (AC-3) 200 kW at 690 V AC 50/60 Hz (AC-3) 160 kW at 1000 V AC 50/60 Hz (AC-3) 75 kW at 230 V AC 50/60 Hz (AC-4) 132 kW at 400 V AC 50/60 Hz (AC-4) 132 kW at 415 V AC 50/60 Hz (AC-4) 150 kW at 440 V AC 50/60 Hz (AC-4) 160 kW at 500 V AC 50/60 Hz (AC-4) 160 kW at 690 V AC 50/60 Hz (AC-4) 160 kW at 1000 V AC 50/60 Hz (AC-4)

Motor power hp

75 hp at 200/208 V 60 Hz 100 hp at 230/240 V 60 Hz 200 hp at 460/480 V 60 Hz 200 hp at 575/600 V 60 Hz

Coil technology

Built-in bidirectional peak limiting

Mechanical durability

8 Mcycles

inrush power in VA (50/60 Hz, AC)

530 VA

inrush power in W (DC)

300 W

hold-in power consumption in VA (50/60 Hz, AC)

16.1 VA

hold-in power consumption in W (DC)

9.0 W

Operating time

40...70 ms closing 15...50 ms opening

Maximum operating rate

600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4

Connections - terminals

Power circuit: bar 2 - busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 185 mm² Power circuit: bolted connection Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end Control circuit: push-in 2 0.5…1.0 mm² with cable end Control circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end

Connection pitch

45 mm

mounting support

Plate

standards

EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1

product certifications

CB Scheme CCC cULus EAC CE UKCA EU-RO-MR by DNV-GL

Tightening torque

35 N.m

height

290 mm

Width

140 mm

Depth

226 mm

Net weight

8.2 kg

IP degree of protection

IP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106

Ambient air temperature for operation

-25…60 °C

Ambient air temperature for storage

-60…80 °C

Mechanical robustness

Vibrations 5…300 Hz 2 gn contactor open Vibrations 5…300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed

Colour

Dark grey

Protective treatment

TH

Permissible ambient air temperature around the device

-40…70 °C at Uc

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

31.000 cm

Package 1 Width

22.500 cm

Package 1 Length

37.200 cm

Package 1 Weight

8.638 kg

Unit Type of Package 2

P06

Number of Units in Package 2

4

Package 2 Height

75.000 cm

Package 2 Width

60.000 cm

Package 2 Length

80.000 cm

Package 2 Weight

44.552 kg

Warranty

18 months

Document Links

Datasheet