Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1
TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 225A 132kW@440V. It provides a 24-48V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 108mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
Range
TeSys
Range of product
TeSys Giga
Product or component type
Contactor
Device short name
LC1G
contactor application
Power switching Motor control
utilisation category
AC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8a AC-8b DC-1 DC-3 DC-5
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Ie] rated operational current
330 A (at <40 °C) at <= 1000 V AC-1 225 A (at <60 °C) at <= 400 V AC-3
[Uc] control circuit voltage
24...48 V AC 50/60 Hz 24...48 V DC
Control circuit voltage limits
Operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
330 A (at 40 °C)
Rated breaking capacity
2050 A at 440 V
[Icw] rated short-time withstand current
1.8 kA - 10 s 1.0 kA - 30 s 0.85 kA - 1 min 0.56 kA - 3 min 0.44 kA - 10 min
Associated fuse rating
250 A aM at <= 440 V for motor 200 A aM at <= 690 V for motor 400 A gG at <= 690 V
Average impedance
0.00015 Ohm
[Ui] rated insulation voltage
1000 V
Power dissipation per pole
20 W AC-1 - Ith 330 A 8 W AC-3 - Ith 225 A
Compatibility code
LC1G
Pole contact composition
3 NO
Auxiliary contact composition
1 NO + 1 NC
Motor power kW
55 kW at 230 V AC 50/60 Hz (AC-3e) 110 kW at 400 V AC 50/60 Hz (AC-3e) 110 kW at 415 V AC 50/60 Hz (AC-3e) 132 kW at 440 V AC 50/60 Hz (AC-3e) 132 kW at 500 V AC 50/60 Hz (AC-3e) 160 kW at 690 V AC 50/60 Hz (AC-3e) 132 kW at 1000 V AC 50/60 Hz (AC-3e) 55 kW at 230 V AC 50/60 Hz (AC-3) 110 kW at 400 V AC 50/60 Hz (AC-3) 110 kW at 415 V AC 50/60 Hz (AC-3) 132 kW at 440 V AC 50/60 Hz (AC-3) 132 kW at 500 V AC 50/60 Hz (AC-3) 160 kW at 690 V AC 50/60 Hz (AC-3) 132 kW at 1000 V AC 50/60 Hz (AC-3) 55 kW at 230 V AC 50/60 Hz (AC-4) 110 kW at 400 V AC 50/60 Hz (AC-4) 110 kW at 415 V AC 50/60 Hz (AC-4) 129 kW at 440 V AC 50/60 Hz (AC-4) 132 kW at 500 V AC 50/60 Hz (AC-4) 132 kW at 690 V AC 50/60 Hz (AC-4) 110 kW at 1000 V AC 50/60 Hz (AC-4)
Motor power hp
60 hp at 200/208 V 60 Hz 75 hp at 230/240 V 60 Hz 150 hp at 460/480 V 60 Hz 150 hp at 575/600 V 60 Hz
Irms rated making capacity
2720 A at 440 V
Coil technology
Built-in bidirectional peak limiting
Mechanical durability
8 Mcycles
inrush power in VA (50/60 Hz, AC)
290 VA
inrush power in W (DC)
220 W
hold-in power consumption in VA (50/60 Hz, AC)
10 VA
hold-in power consumption in W (DC)
5.7 W
Operating time
40...70 ms closing 15...50 ms opening
Maximum operating rate
600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4
Connections - terminals
Power circuit: bar 2 - busbar cross section: 25 x 6 mm Power circuit: lugs-ring terminals 1 185 mm² Power circuit: bolted connection Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end Control circuit: push-in 2 0.5…1.0 mm² with cable end Control circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end
Connection pitch
35 mm
mounting support
Plate
standards
EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1
product certifications
CB Scheme CCC cULus EAC CE UKCA EU-RO-MR by DNV-GL
Tightening torque
18 N.m
height
255 mm
Width
108 mm
Depth
193 mm
Net weight
4.1 kg
IP degree of protection
IP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106
Ambient air temperature for operation
-25…60 °C
Ambient air temperature for storage
-60…80 °C
Mechanical robustness
Vibrations 5…300 Hz 2 gn contactor open Vibrations 5…300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
Colour
Dark grey
Protective treatment
TH
Permissible ambient air temperature around the device
-40…70 °C at Uc
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
23.0 cm
Package 1 Width
25.0 cm
Package 1 Length
38.5 cm
Package 1 Weight
5.267 kg
Unit Type of Package 2
S06
Number of Units in Package 2
6
Package 2 Height
75.0 cm
Package 2 Width
60.0 cm
Package 2 Length
80.0 cm
Package 2 Weight
45.0 kg
Warranty
18 months