Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1
TeSys F contactor, 3 poles (3NO), 2100A/1000V AC-1, for non-inductive load applications. It provides a low sealed consumption 230V 40-400Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 600 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC), Green Premium compliant (RoHS/REACh).
Range
TeSys
Range of product
TeSys F
Product or component type
Contactor
Device short name
LC1F
contactor application
Resistive load
utilisation category
AC-1
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Uc] control circuit voltage
230 V AC 40...400 Hz
[Ie] rated operational current
2100 A (at <40 °C) AC AC-1
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
2100 A (at 40 °C)
Rated breaking capacity
3150 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
10000 A 40 °C - 10 s 7500 A 40 °C - 30 s 5500 A 40 °C - 1 min 4200 A 40 °C - 3 min 3000 A 40 °C - 10 min
Associated fuse rating
2000 A gG at <= 440 V
Average impedance
0.1 mOhm - Ith 2100 A 50 Hz
[Ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C 1000 V conforming to UL 60947-4-1
Power dissipation per pole
200 W AC-1
Overvoltage category
III
power pole contact composition
3 NO
Control circuit voltage limits
Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.3...0.5 Uc 40...400 Hz (at 55 °C)
Inrush power in VA
2200 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
Hold-in power consumption in VA
36 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
Maximum operating rate
600 cyc/h 55 °C
Operating time
100...170 ms opening 40...75 ms closing
Connections - terminals
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: bar 4 cable(s) - busbar cross section: 100 x 5 mm Power circuit: bolted connection
Tightening torque
Control circuit: 1.2 N.m Power circuit: 58 N.m
mounting support
Plate
Heat dissipation
36 W
standards
EN 60947-1 JIS C8201-4-1 EN 60947-4-1 IEC 60947-4-1 IEC 60947-1 UL 60947-4-1 CSA C22.2 No 60947-4-1
product certifications
UL CSA CCC CB Scheme EAC UKCA
Compatibility code
LC1F
Control circuit type
AC at 40...400 Hz
Protective treatment
TH
Ambient air temperature for operation
-5…40 °C
Ambient air temperature for storage
-60…80 °C
Permissible ambient air temperature around the device
-40…60 °C
height
332 mm
Width
438 mm
Depth
238.6 mm
Operating altitude
3000 m without derating
Net weight
31 kg
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
38 cm
Package 1 Width
48 cm
Package 1 Length
60 cm
Package 1 Weight
40 kg
Warranty
18 months