Trade Price
£3,645.22
Per
1
Unit
EA
Pack Quantity
1
This is 400A, 4 poles 4d, 36kA at 800VAC ComPacT NSX400K circuit breaker with MicroLogic 2.3 trip unit.
Range
ComPacT
Range of product
ComPact NSX400...630
Device short name
ComPacT NSX400K
Product or component type
Circuit breaker
Device application
Special application
Number of poles
4P
Protected poles description
3t 3t + N/2 4t
Neutral position
Left
[In] rated current
400 A at 40 °C
[Ue] rated operational voltage
800...1000 V AC 50/60 Hz
Network type
AC
Network frequency
50/60 Hz
Suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
36 kA Icu at 800 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 1000 V AC 50/60 Hz conforming to IEC 60947-2
Performance level
K 10 kA 1000 V AC
Trip unit name
MicroLogic 2.3
Trip unit technology
Electronic
Trip unit protection functions
LSoI
Control type
Toggle
Circuit breaker mounting mode
Fixed
[Ui] rated insulation voltage
1000 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ics] rated service short-circuit breaking capacity
10 kA at 800 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 1000 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability
15000 cycles
Electrical durability
1000 cycles at 1000 V In
mounting support
Backplate
Upside connection
Front
downside connection
Front
Connection pitch
45 mm
Protection type
L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rating
400 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
160...400 A
Long-time protection delay adjustment type tr
Fixed
[tr] long-time protection delay adjustment range
11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir
Thermal memory
20 minutes before and after tripping
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5...10 x Ir
Short-time protection delay adjustment type tsd
Fixed
Instantaneous protection pick-up adjustment type Ii
Fixed
[Ii] instantaneous protection pick-up adjustment range
4800 A
earth-leakage protection
Without
Neutral protection settings
0.5 x Ir (3t + N/2) 1 x Ir (4t) No protection (3t)
Zone selective interlocking ZSI
Without
Number of slots for electrical auxiliaries
6 slot(s)
Local signalling
Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Width (W)
185 mm
Height (H)
255 mm
Depth (D)
110 mm
Net weight
7.9 kg
standards
EN/IEC 60947
product certifications
CE CCC
Overvoltage category
IV
Electrical shock protection class
Class II
Pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Relative humidity
0…95 %
Operating altitude
0...2000 m without derating 2000 m...5000 m with derating
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
19.4 cm
Package 1 Width
15.8 cm
Package 1 Length
33.0 cm
Package 1 Weight
6.5 kg
Warranty
18 months