Trade Price
£2,685.55
Per
1
Unit
EA
Pack Quantity
1
This MicroLogic 7.3 E (Energy) is a 3 poles 3d electronic trip unit used on ComPacT NSX 630 circuit breakers. This 570A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. MicroLogic 7.3 E Vigi trip unit offers an integrated adjustable earth-leakage protection. MicroLogic 7.3 E indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. MicroLogic 7.3 E is equipped with a display module that gives energy measurement and allows fine adjustment settings. An earth leakage pre-alarm can be remotely available by installing the optional SDx module (LV429532). This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and ComPacT NSX basic frame.
Range
ComPacT new generation
Range of product
ComPacT NSX400...630 new generation
Product or component type
Trip unit
Trip unit name
MicroLogic 7.3 E
Trip unit technology
Electronic
Range compatibility
ComPacT new generation NSX630
Device application
Distribution
Poles description
3P
Protected poles description
3D
Trip unit protection functions
LSIR
Protection type
L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection R : for earth-leakage protection
Trip unit rating
570 A at 40 °C
[Ue] rated operational voltage
440 V AC 50/60 Hz
Network type
AC
Network frequency
50/60 Hz
Circuit breaker mounting mode
Fixed
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
250...570 A
Long-time protection delay adjustment type tr
Adjustable
[tr] long-time protection delay adjustment range
15…400 s at 1.5 x Ir 0.35…11 s at 7.2 x Ir 0.5…16 s at 6 x Ir
Thermal memory
20 minutes before and after tripping
Short-time protection pick-up adjustment type Isd
Adjustable
[Isd] Short-time protection pick-up adjustment range
1.5...10 x Ir
Short-time protection delay adjustment type tsd
Adjustable
[tsd] Short-time protection delay adjustment range
0…0.4 s I²t=off 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type Ii
Adjustable
[Ii] instantaneous protection pick-up adjustment range
1.5...11 x In
earth-leakage protection
Integrated
Earth-leakage protection class
Class A
Earth-leakage protection sensitity adjustment type IΔn
Adjustable
[IΔn] earth-leakage protection sensitivity adjustment range
0.3 A 0.5 A 1 A 3 A 5 A 10 A
Earth-leakage protection specific mode
OFF using the IΔn rotary switch
Earth-leakage protection time delay adjustement type Δt
Adjustable
[Δt] Earth-leakage protection time delay adjustment range
0 ms 60 ms 150 ms 500 ms 1 s
Zone selective interlocking ZSI
Without
Local signalling
Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Display type
LCD display
Type of measurement
Energy meter
communication of data
Power quality Earth leakage current Protection and alarm settings Maintenance indicators Maximeters/minimeters Energy metering Demand current and power Instantaneous and demand values Test reports Time-stamped histories and event tables
standards
EN/IEC 60947-2
Electrical shock protection class
Class II
Pollution degree
3 conforming to IEC 60947-1
IP degree of protection
IP40 conforming to IEC 60529
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
16.800 cm
Package 1 Width
21.400 cm
Package 1 Length
24.900 cm
Package 1 Weight
1.887 kg
Unit Type of Package 2
S03
Number of Units in Package 2
2
Package 2 Height
30.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
4.130 kg
Warranty
18 months
Datasheet