C40N4

NSX400N 4P 50kA Frame

Trade Price

£1,011.92

Per

1

Unit

EA

Pack Quantity

1

C40N4

Information

This is a 4 poles basic frame for ComPacT NSX400N. ComPacT NSX is designed to optimize space and breaking capacity for all standard and specific applications. This basic frame comes without trip unit, and is compatible with any type of trip unit which has to be ordered separately The breaking capacity Icu is 50kA at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz (limited to 440VAC 50/60Hz if there is an earth-leakage protection). It can be equipped with a variety of optional functions and accessories. The dimensions are 185mm x 255mm x 110mm. It ensures compliance with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX400N is part of Schneider Electric EcoStruxure Power architecture.

Technical Specifications

Range

ComPacT new generation

Product name

ComPacT NSX new generation

Device short name

NSX400N

Product or component type

Basic frame

Device application

Distribution

Poles description

4P

Neutral position

Left

[In] rated current

400 A at 40 °C

[Ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

Network type

AC

Network frequency

50/60 Hz

Suitability for isolation

Yes conforming to EN/IEC 60947-2

utilisation category

Category A

[Icu] rated ultimate short-circuit breaking capacity

85 kA at 240 V AC 50/60 Hz conforming to UL 508 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 480 V AC 50/60 Hz conforming to UL 508 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 600 V AC 50/60 Hz conforming to UL 508 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2

Performance level

N 50 kA 415 V AC

Control type

Toggle

Mounting mode

Fixed

[Ui] rated insulation voltage

800 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

8 kV conforming to IEC 60947-2

[Ics] rated service short-circuit breaking capacity

11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability

15000 cycles conforming to IEC 60947-2

Electrical durability

12000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 3000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 6000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 6000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2

mounting support

Backplate

Upside connection

Front

downside connection

Front

Connection pitch

45 mm

Protection type

Without protection

Width (W)

185 mm

Height (H)

255 mm

Depth (D)

110 mm

standards

EN/IEC 60947-2 UL 508

product certifications

UL CSA

Pollution degree

3 conforming to IEC 60664-1

IP degree of protection

IP40 conforming to IEC 60529

IK degree of protection

IK07 conforming to IEC 62262

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-50…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

15.000 cm

Package 1 Width

20.000 cm

Package 1 Length

29.000 cm

Package 1 Weight

5.818 kg

Unit Type of Package 2

P12

Number of Units in Package 2

28

Package 2 Height

44.000 cm

Package 2 Width

80.000 cm

Package 2 Length

120.000 cm

Package 2 Weight

176.000 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet