C25W35E160

NSX250HB2 3P 100kA ML 5.2 E 160A

Trade Price

£3,372.58

Per

1

Unit

EA

Pack Quantity

1

C25W35E160

Information

This ComPacT NSX250HB2 is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 100kA rms at 500VAC 50/60Hz and 100kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic MicroLogic 5.2 E trip unit, with 160A rating. MicroLogic 5.2 E trip unit provides adjustable long time, short time and instantaneous protection. MicroLogic 5.2 E has an embedded display unit for fine settings adjustment and display of the energy (energy meter). This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX250HB2 is part of Schneider Electric EcoStruxure Power architecture.

Technical Specifications

Range

ComPacT new generation

Product name

ComPacT NSX new generation

Device short name

NSX250HB2

Product or component type

Circuit breaker

Device application

Distribution

Poles description

3P

Protected poles description

3D

[In] rated current

160 A at 40 °C

[Ue] rated operational voltage

690 V AC 50/60 Hz

Network type

AC

Network frequency

50/60 Hz

Suitability for isolation

Yes conforming to EN/IEC 60947-2

utilisation category

Category A

[Icu] rated ultimate short-circuit breaking capacity

100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

Performance level

HB2 100 kA 690 V AC

Trip unit name

MicroLogic 5.2 E

Trip unit technology

Electronic

Trip unit protection functions

LSI

Control type

Toggle

Circuit breaker mounting mode

Fixed

[Ui] rated insulation voltage

800 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage

8 kV

[Ics] rated service short-circuit breaking capacity

100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability

20000 cycles

Electrical durability

20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In

Power dissipation per pole

7.17 W

mounting support

Backplate

Mounting position

Horizontal and vertical Flat on the back

Upside connection

Front

downside connection

Front

Connection pitch

35 mm

Protection type

L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection

Trip unit rating

160 A at 40 °C

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

63...160 A

Long-time protection delay adjustment type tr

Adjustable

[tr] long-time protection delay adjustment range

15…400 s at 1.5 x Ir 0.5…16 s at 6 x Ir 0.35…11 s at 7.2 x Ir

Thermal memory

20 minutes before and after tripping

Short-time protection pick-up adjustment type Isd

Adjustable 9 settings

[Isd] Short-time protection pick-up adjustment range

1.5...10 x Ir

Short-time protection delay adjustment type tsd

Adjustable 5 settings

[tsd] Short-time protection delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

Instantaneous protection pick-up adjustment type Ii

Adjustable

[Ii] instantaneous protection pick-up adjustment range

1.5...15 x In

earth-leakage protection

Without

Zone selective interlocking ZSI

With

Number of slots for electrical auxiliaries

5 slot(s)

Local signalling

Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload

Display type

LCD display

Type of measurement

Energy meter

communication of data

Time-stamped histories and event tables Instantaneous and demand values Maintenance indicators Power quality Demand current and power Protection and alarm settings Energy metering Maximeters/minimeters

Width (W)

105 mm

Height (H)

161 mm

Depth (D)

86 mm

Net weight

2.4 kg

standards

EN/IEC 60947

product certifications

CCC Marine EAC

Overvoltage category

Class II

Electrical shock protection class

Class II

Pollution degree

3 conforming to IEC 60664-1

IP degree of protection

IP40 conforming to IEC 60529

IK degree of protection

IK07 conforming to IEC 62262

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Relative humidity

0…95 %

Operating altitude

0...2000 m without derating 2000 m...5000 m with derating

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

12.0 cm

Package 1 Width

14.0 cm

Package 1 Length

19.0 cm

Package 1 Weight

2.065 kg

Unit Type of Package 2

S03

Number of Units in Package 2

4

Package 2 Height

30.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

8.26 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet