Trade Price
£459.02
Per
1
Unit
EA
Pack Quantity
1
This is a 3 poles basic frame for ComPacT NSX250N. ComPacT NSX is designed to optimize space and breaking capacity for all standard and specific applications. This basic frame comes without trip unit, and is compatible with any type of trip unit which has to be ordered separately The breaking capacity Icu is 50kA at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz (limited to 440VAC 50/60Hz if there is an earth-leakage protection). It can be equipped with a variety of optional functions and accessories. The dimensions are 105mm x 161mm x 86mm. It ensures compliance with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX250N is part of Schneider Electric EcoStruxure Power architecture.
Range
ComPacT new generation
Product name
ComPacT NSX new generation
Device short name
NSX250N
Product or component type
Basic frame
Device application
Distribution
Poles description
3P
[In] rated current
250 A at 40 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
Network type
AC
Network frequency
50/60 Hz
Suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
85 kA at 240 V AC 50/60 Hz conforming to UL 508 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 480 V AC 50/60 Hz conforming to UL 508 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 600 V AC 50/60 Hz conforming to UL 508
Performance level
N 50 kA 415 V AC
control type
Toggle
Mounting mode
Fixed
[Ui] rated insulation voltage
800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability
20000 cycles conforming to IEC 60947-2
Electrical durability
10000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 10000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 20000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 5000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
mounting support
Backplate
Upside connection
Front
downside connection
Front
Connection pitch
35 mm
Protection type
Without protection
Width (W)
105 mm
Height (H)
161 mm
Depth (D)
86 mm
Standards
EN/IEC 60947-2 UL 508
product certifications
UL CSA
Pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
14 cm
Package 1 Width
11 cm
Package 1 Length
19.5 cm
Package 1 Weight
1.584 kg
Unit Type of Package 2
S03
Number of Units in Package 2
7
Package 2 Height
30 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
11.538 kg
Unit Type of Package 3
P12
Number of Units in Package 3
56
Package 3 Height
43 cm
Package 3 Width
80 cm
Package 3 Length
120 cm
Package 3 Weight
104 kg
Warranty
18 months
Datasheet