Trade Price
£2,161.70
Per
1
Unit
EA
Pack Quantity
1
This ComPacT NSX250 is a complete 4P fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 50kA rms at 1500DC. The operational voltage is 1500VDC. This product embeds a 200A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection.
Range
ComPacT new generation
Product name
ComPacT NSX DC EP
Device short name
NSX250 DC EP
Product or component type
Circuit breaker
Device application
Photovoltaic Marine application
Poles description
4P
[In] rated current
200 A at 40 °C
[Ue] rated operational voltage
1500 V DC
Network type
DC
Suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
20 kA Icu at 1500 V DC 4 poles in series conforming to IEC 60947-2 50 kA Icu at 1100 V DC 4 poles in series conforming to IEC 60947-2
Performance level
F 20 kA 1500 V DC
Trip unit name
TM-DC
Trip unit technology
Thermal-magnetic
Trip unit protection functions
LI
Control type
Toggle
Circuit breaker mounting mode
Fixed
[Ui] rated insulation voltage
1600 V DC conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
20 kA at 1500 V DC conforming to IEC 60947-2 20 kA at 1100 V DC conforming to IEC 60947-2
Mechanical durability
10000 cycles
Electrical durability
4500 cycles at 1500 V In
mounting support
Backplate
Mounting position
Horizontal and vertical Flat on the back
Upside connection
Front
downside connection
Front
Protection type
L : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rating
200 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable
[Ir] long-time protection pick-up adjustment range
0.7...1 x In
Long-time protection delay adjustment type tr
Fixed
Instantaneous protection pick-up adjustment type Ii
Fixed
[Ii] instantaneous protection pick-up adjustment range
1200 A
earth-leakage protection
Without
Width (W)
140 mm
Height (H)
161 mm
Depth (D)
86 mm
Net weight
2.8 kg
standards
EN/IEC 60947
product certifications
CCC
Pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Relative humidity
0…95 %
Operating altitude
0...2000 m without derating 2000 m...5000 m with derating
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
13.5 cm
Package 1 Width
14.5 cm
Package 1 Length
19 cm
Package 1 Weight
2.8 kg
Unit Type of Package 2
S03
Number of Units in Package 2
4
Package 2 Height
30 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
11.641 kg
Unit Type of Package 3
P06
Number of Units in Package 3
32
Package 3 Height
75 cm
Package 3 Width
60 cm
Package 3 Length
80 cm
Package 3 Weight
98.9 kg
Warranty
18 months