Trade Price
£1,610.29
Per
1
Unit
EA
Pack Quantity
1
This ComPacT NSX100HB2 is a complete 4P 4d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 100kA rms at 500VAC 50/60Hz and 100kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic MicroLogic 2.2 trip unit, with 100A rating. MicroLogic 2.2 trip unit provides adjustable long time and short time protections, and a fixed instantaneous protection. This 4 poles version (140mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX100HB2 is part of Schneider Electric EcoStruxure Power architecture.
Range
ComPacT new generation
Product name
ComPacT NSX new generation
Device short name
NSX100HB2
Product or component type
Circuit breaker
Device application
Distribution
Poles description
4P
Protected poles description
4D 3D + N/2 3D
Neutral position
Left
[In] rated current
100 A at 40 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
Network type
AC
Network frequency
50/60 Hz
Suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Performance level
HB2 100 kA 690 V AC
Trip unit name
MicroLogic 2.2
Trip unit technology
Electronic
Trip unit protection functions
LSoI
control type
Toggle
Circuit breaker mounting mode
Fixed
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ics] rated service short-circuit breaking capacity
100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability
20000 cycles
Electrical durability
20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Power dissipation per pole
4.7 W
mounting support
Backplate
Mounting position
Horizontal and vertical Flat on the back
Upside connection
Front
downside connection
Front
Connection pitch
35 mm
Protection type
L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rating
100 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
40...100 A
Long-time protection delay adjustment type tr
Fixed
[tr] long-time protection delay adjustment range
400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir
Neutral protection settings
0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)
thermal memory
20 minutes before and after tripping
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5...10 x Ir
Short-time protection delay adjustment type tsd
Fixed
Instantaneous protection pick-up adjustment type Ii
Fixed
[Ii] instantaneous protection pick-up adjustment range
1500 A
earth-leakage protection
Without
Zone selective interlocking ZSI
Without
Number of slots for electrical auxiliaries
5 slot(s)
Local signalling
Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Width (W)
140 mm
Height (H)
161 mm
Depth (D)
86 mm
Net weight
2.4 kg
Standards
EN/IEC 60947
product certifications
EAC Marine CCC
Overvoltage category
Class II
Electrical shock protection class
Class II
Pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Relative humidity
0…95 %
Operating altitude
0...2000 m without derating 2000 m...5000 m with derating
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
14.0 cm
Package 1 Width
15.0 cm
Package 1 Length
20.0 cm
Package 1 Weight
2.42 kg
Unit Type of Package 2
S03
Number of Units in Package 2
4
Package 2 Height
30.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
9.68 kg
Warranty
18 months
Datasheet