C1BN2TM800D

NSX800 DC 2P 50kA TM-DC 800A

Trade Price

£2,473.84

Per

1

Unit

EA

Pack Quantity

1

C1BN2TM800D

Information

ComPacT NSX1200N DC is a complete 2 poles fixed circuit breaker designed to optimize space and breaking capacity. It's an optimal choice for applications using DC voltages. The breaking capacity (Icu) is 50kA rms at 600VDC. The operational voltage is 600VDC. This product embeds a 800A rating thermal-magnetic trip unit (TM-DC). TM-DC trip unit provides an adjustable thermal overload protection and an adjustable magnetic protection. The dimension is 350mm x 185mm x 110mm (H x W x D). It is compliant with international standards (EN/IEC 60947), CCC, EAC and marine specifications.

Technical Specifications

Range

ComPacT new generation

Product name

ComPacT NSX DC new generation

Device short name

NSX1200 DC

Product or component type

Circuit breaker

Device application

Distribution

Poles description

2P

Protected poles description

2D

[In] rated current

800 A at 40 °C

[Ue] rated operational voltage

600 V DC

Network type

DC

Suitability for isolation

Yes conforming to EN/IEC 60947-2

utilisation category

Category A

[Icu] rated ultimate short-circuit breaking capacity

50 kA Icu at 24...300 V DC 1 pole conforming to IEC 60947-2 50 kA Icu at 300...600 V DC 2 poles in series conforming to IEC 60947-2

Performance level

N 50 kA 600 V DC

Trip unit name

TM-DC

Trip unit technology

Thermal-magnetic

Trip unit protection functions

LI

Control type

Toggle

Circuit breaker mounting mode

Fixed

[Ui] rated insulation voltage

750 V DC conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

8 kV conforming to IEC 60947-2

[Ics] rated service short-circuit breaking capacity

12.5 kA at 24...300 V DC conforming to IEC 60947-2 12.5 kA at 300...600 V DC conforming to IEC 60947-2

Mechanical durability

5000 cycles

Electrical durability

2000 cycles at 600 V In/2 1000 cycles at 600 V In

mounting support

Backplate

Mounting position

Horizontal and vertical Flat on the back

Upside connection

Front

downside connection

Front

Connection pitch

45 mm

Protection type

L : for overload protection (thermal) I : for short-circuit protection (magnetic)

Trip unit rating

800 A at 40 °C

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable

[Ir] long-time protection pick-up adjustment range

0.7...1 x In

Long-time protection delay adjustment type tr

Fixed

Instantaneous protection pick-up adjustment type Ii

Adjustable

[Ii] instantaneous protection pick-up adjustment range

2.5...5 x In

earth-leakage protection

Without

Number of slots for electrical auxiliaries

6 slot(s)

Width (W)

185 mm

Height (H)

485 mm

Depth (D)

110 mm

Net weight

9.4 kg

standards

EN/IEC 60947-2

product certifications

CCC EAC Marine

Overvoltage category

Class II

Electrical shock protection class

Class II

Pollution degree

3 conforming to IEC 60664-1

IP degree of protection

IP40 conforming to IEC 60529

IK degree of protection

IK07 conforming to IEC 62262

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-50…85 °C

Relative humidity

0…95 %

Operating altitude

0...2000 m without derating 2000 m...5000 m with derating

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

30.0 cm

Package 1 Width

40.0 cm

Package 1 Length

60.0 cm

Package 1 Weight

10.182 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet