C63S3TM600D

NSX630S DC 3P 100kA TM-DC 600A

Trade Price

£2,151.14

Per

1

Unit

EA

Pack Quantity

1

C63S3TM600D

Information

ComPacT NSX 600S DC is a complete 3 poles fixed circuit breaker designed to optimize space and breaking capacity. It's an optimal choice for applications using DC voltages. The breaking capacity (Icu) is 100kA rms at 750VDC. The operational voltage is 750VDC. This product embeds a 600A rating thermal-magnetic trip unit (TM-DC). TM-DC trip unit provides an adjustable thermal overload protection and an adjustable magnetic protection. The dimension is 255mm x 140mm x 110mm (H x W x D). It is compliant with international standard EN/IEC 60947.

Technical Specifications

Range

ComPacT new generation

Product name

ComPacT NSX DC new generation

Device short name

NSX630S DC

Product or component type

Circuit breaker

Device application

Distribution

Poles description

3P

Protected poles description

3D

[In] rated current

600 A at 40 °C

[Ue] rated operational voltage

750 V DC

Network type

DC

Suitability for isolation

Yes conforming to EN/IEC 60947-2

utilisation category

Category A

[Icu] rated ultimate short-circuit breaking capacity

100 kA Icu at 24...125 V DC 1 pole conforming to IEC 60947-2 100 kA Icu at 250 V DC 1 pole conforming to IEC 60947-2 100 kA Icu at 500 V DC 2 poles in series conforming to IEC 60947-2 100 kA Icu at 750 V DC 3 poles in series conforming to IEC 60947-2

Performance level

S 100 kA 500 V DC

Trip unit name

TM-DC

Trip unit technology

Thermal-magnetic

Trip unit protection functions

LI

Control type

Toggle

Circuit breaker mounting mode

Fixed

[Ui] rated insulation voltage

750 V DC conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

8 kV conforming to IEC 60947-2

[Ics] rated service short-circuit breaking capacity

100 kA at 24...125 V DC conforming to IEC 60947-2 100 kA at 250 V DC conforming to IEC 60947-2 100 kA at 500 V DC conforming to IEC 60947-2 100 kA at 750 V DC conforming to IEC 60947-2

Mechanical durability

5000 cycles

Electrical durability

2000 cycles at 750 V In/2 1000 cycles at 750 V In

mounting support

Backplate

Mounting position

Horizontal and vertical Flat on the back

Upside connection

Front

downside connection

Front

Connection pitch

45 mm

Protection type

L : for overload protection (thermal) I : for short-circuit protection (magnetic)

Trip unit rating

600 A at 40 °C

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable

[Ir] long-time protection pick-up adjustment range

0.7...1 x In

Long-time protection delay adjustment type tr

Fixed

Instantaneous protection pick-up adjustment type Ii

Adjustable

[Ii] instantaneous protection pick-up adjustment range

2.5...5 x In

earth-leakage protection

Without

Number of slots for electrical auxiliaries

6 slot(s)

Width (W)

140 mm

Height (H)

255 mm

Depth (D)

110 mm

Net weight

8.0 kg

standards

EN/IEC 60947

product certifications

CCC EAC Marine

Overvoltage category

Class II

Electrical shock protection class

Class II

Pollution degree

3 conforming to IEC 60664-1

IP degree of protection

IP40 conforming to IEC 60529

IK degree of protection

IK07 conforming to IEC 62262

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-50…85 °C

Relative humidity

0…95 %

Operating altitude

0...2000 m without derating 2000 m...5000 m with derating

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

15.000 cm

Package 1 Width

15.500 cm

Package 1 Length

29.500 cm

Package 1 Weight

5.500 kg

Unit Type of Package 2

S04

Number of Units in Package 2

2

Package 2 Height

30.000 cm

Package 2 Width

40.000 cm

Package 2 Length

60.000 cm

Package 2 Weight

11.703 kg

Unit Type of Package 3

P12

Number of Units in Package 3

8

Package 3 Height

45.000 cm

Package 3 Width

80.000 cm

Package 3 Length

120.000 cm

Package 3 Weight

58.812 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet