Trade Price
£887.19
Per
1
Unit
EA
Pack Quantity
1
This ComPacT NSX100HB1 is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 85kA rms at 500VAC 50/60Hz and 75kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 100A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX100HB1 is part of Schneider Electric EcoStruxure Power architecture.
Range
ComPacT new generation
Product name
ComPacT NSX new generation
Device short name
NSX100HB1
Product or component type
Circuit breaker
Device application
Distribution
Poles description
3P
Protected poles description
3D
[In] rated current
100 A at 40 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
Network type
AC
Network frequency
50/60 Hz
Suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Performance level
HB1 75 kA 690 V AC
Trip unit name
TM-D
Trip unit technology
Thermal-magnetic
Trip unit protection functions
LI
control type
Toggle
Circuit breaker mounting mode
Fixed
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ics] rated service short-circuit breaking capacity
85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability
20000 cycles
Electrical durability
20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Power dissipation per pole
8.8 W
mounting support
Backplate
Mounting position
Horizontal and vertical Flat on the back
Upside connection
Front
downside connection
Front
Connection pitch
35 mm
Protection type
L : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rating
100 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable
[Ir] long-time protection pick-up adjustment range
0.7...1 x In
Long-time protection delay adjustment type tr
Fixed
[tr] long-time protection delay adjustment range
120…400 s at 1.5 x In 15 s at 6 x Ir
Instantaneous protection pick-up adjustment type Ii
Fixed
[Ii] instantaneous protection pick-up adjustment range
800 A
earth-leakage protection
Without
Number of slots for electrical auxiliaries
5 slot(s)
Width (W)
105 mm
Height (H)
161 mm
Depth (D)
86 mm
Net weight
2.05 kg
Standards
EN/IEC 60947
product certifications
EAC Marine CCC
Overvoltage category
Class II
Electrical shock protection class
Class II
Pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Relative humidity
0…95 %
Operating altitude
0...2000 m without derating 2000 m...5000 m with derating
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
12.0 cm
Package 1 Width
15.0 cm
Package 1 Length
19.0 cm
Package 1 Weight
1.8 kg
Unit Type of Package 2
S03
Number of Units in Package 2
7
Package 2 Height
30.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
14.54 kg
Warranty
18 months
Datasheet