Trade Price
£1,071.07
Per
1
Unit
EA
Pack Quantity
1
This ComPacT NSX100HB1 is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for motor protection applications. The breaking capacity (Icu) is 85kA rms at 500VAC 50/60Hz and 75kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic MicroLogic 2.2 M trip unit, with 50A rating. MicroLogic 2.2 M trip unit provides adjustable long time and short time protections, and fixed instantaneous protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX100HB1 is part of Schneider Electric EcoStruxure Power architecture.
Range
ComPacT new generation
Product name
ComPacT NSX new generation
Device short name
NSX100HB1
Product or component type
Circuit breaker
Device application
Motor protection
Poles description
3P
Protected poles description
3D
[In] rated current
50 A at 65 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
Network type
AC
Network frequency
50/60 Hz
Suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Performance level
HB1 75 kA 690 V AC
Trip unit name
MicroLogic 2.2 M
Trip unit technology
Electronic
Trip unit protection functions
LSoI
control type
Toggle
Circuit breaker mounting mode
Fixed
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ics] rated service short-circuit breaking capacity
85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability
20000 cycles
Electrical durability
20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Power dissipation per pole
1.18 W
mounting support
Backplate
Mounting position
Horizontal and vertical Flat on the back
Upside connection
Front
downside connection
Front
Connection pitch
35 mm
Protection type
L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rating
50 A at 65 °C
Motor tripping class
20 5 10
complementary motor protection
Phase unbalance
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
25...50 A
Long-time protection delay adjustment type tr
Fixed
[tr] long-time protection delay adjustment range
120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20
thermal memory
20 minutes before and after tripping
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
5...13 x Ir
Short-time protection delay adjustment type tsd
Fixed
Instantaneous protection pick-up adjustment type Ii
Fixed
[Ii] instantaneous protection pick-up adjustment range
750 A
earth-leakage protection
Without
Zone selective interlocking ZSI
Without
Number of slots for electrical auxiliaries
5 slot(s)
Local signalling
Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
Width (W)
105 mm
Height (H)
161 mm
Depth (D)
86 mm
Net weight
2.05 kg
Standards
EN/IEC 60947
product certifications
CCC Marine EAC
Overvoltage category
Class II
Electrical shock protection class
Class II
Pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Relative humidity
0…95 %
Operating altitude
0...2000 m without derating 2000 m...5000 m with derating
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
11.000 cm
Package 1 Width
20.000 cm
Package 1 Length
14.000 cm
Package 1 Weight
1.877 kg
Warranty
18 months