C25V32M220

NSX250HB1 3P 75kA ML 2.2 M 220A

Trade Price

£2,185.96

Per

1

Unit

EA

Pack Quantity

1

C25V32M220

Information

This ComPacT NSX250HB1 is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for motor protection applications. The breaking capacity (Icu) is 85kA rms at 500VAC 50/60Hz and 75kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic MicroLogic 2.2 M trip unit, with 220A rating. MicroLogic 2.2 M trip unit provides adjustable long time and short time protections, and fixed instantaneous protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX250HB1 is part of Schneider Electric EcoStruxure Power architecture.

Technical Specifications

Range

ComPacT new generation

Product name

ComPacT NSX new generation

Device short name

NSX250HB1

Product or component type

Circuit breaker

Device application

Motor protection

Poles description

3P

Protected poles description

3D

[In] rated current

220 A at 65 °C

[Ue] rated operational voltage

690 V AC 50/60 Hz

Network type

AC

Network frequency

50/60 Hz

Suitability for isolation

Yes conforming to EN/IEC 60947-2

utilisation category

Category A

[Icu] rated ultimate short-circuit breaking capacity

85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

Performance level

HB1 75 kA 690 V AC

Trip unit name

MicroLogic 2.2 M

Trip unit technology

Electronic

Trip unit protection functions

LSoI

Control type

Toggle

Circuit breaker mounting mode

Fixed

[Ui] rated insulation voltage

800 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage

8 kV

[Ics] rated service short-circuit breaking capacity

85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability

20000 cycles

Electrical durability

20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In

Power dissipation per pole

13.55 W

mounting support

Backplate

Mounting position

Horizontal and vertical Flat on the back

Upside connection

Front

downside connection

Front

Connection pitch

35 mm

Protection type

L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection

Trip unit rating

220 A at 65 °C

Motor tripping class

10 5 20

complementary motor protection

Phase unbalance

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

100...220 A

Long-time protection delay adjustment type tr

Fixed

[tr] long-time protection delay adjustment range

120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20

Thermal memory

20 minutes before and after tripping

Short-time protection pick-up adjustment type Isd

Adjustable 9 settings

[Isd] Short-time protection pick-up adjustment range

5...13 x Ir

Short-time protection delay adjustment type tsd

Fixed

Instantaneous protection pick-up adjustment type Ii

Fixed

[Ii] instantaneous protection pick-up adjustment range

3300 A

earth-leakage protection

Without

Zone selective interlocking ZSI

Without

Number of slots for electrical auxiliaries

5 slot(s)

Local signalling

Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point

Width (W)

105 mm

Height (H)

161 mm

Depth (D)

86 mm

Net weight

2.4 kg

standards

EN/IEC 60947

product certifications

CCC Marine EAC

Overvoltage category

Class II

Electrical shock protection class

Class II

Pollution degree

3 conforming to IEC 60664-1

IP degree of protection

IP40 conforming to IEC 60529

IK degree of protection

IK07 conforming to IEC 62262

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-50…85 °C

Relative humidity

0…95 %

Operating altitude

0...2000 m without derating 2000 m...5000 m with derating

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

11 cm

Package 1 Width

14 cm

Package 1 Length

20 cm

Package 1 Weight

2.051 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet