Trade Price
£352.59
Per
1
Unit
EA
Pack Quantity
1
ComPacT NSX 100S is a complete 2 poles fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 75kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 100A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an fixed thermal overload protection and a fixed magnetic protection. The dimension is 161mm x 70mm x 86mm (H x W x D). It is compliant with international standards (EN/IEC 60947), CCC, EAC and marine specifications.
Range
ComPacT new generation
Product name
ComPacT NSX new generation
Device short name
NSX100S
Product or component type
Circuit breaker
Device application
Distribution
Poles description
2P
Protected poles description
2D
[In] rated current
100 A at 40 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz 500 V DC
Network type
AC DC
Network frequency
50/60 Hz
Suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 250 V DC 1 pole conforming to IEC 60947-2 100 kA Icu at 500 V DC 2 poles in series conforming to IEC 60947-2 100 kA Icu at 500 V DC 2P conforming to IEC 60947-2
Performance level
S 70 kA 415 V AC
Trip unit name
TM-D
Trip unit technology
Thermal-magnetic
Trip unit protection functions
LI
Control type
Toggle
Circuit breaker mounting mode
Fixed
[Ui] rated insulation voltage
750 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 250 V DC conforming to IEC 60947-2 100 kA at 500 V DC conforming to IEC 60947-2
Mechanical durability
20000 cycles
Electrical durability
20000 cycles at 277 V In/2 10000 cycles at 277 V In
Power dissipation per pole
8.8 W
mounting support
Backplate
Mounting position
Horizontal and vertical Flat on the back
Upside connection
Front
downside connection
Front
Connection pitch
35 mm
Protection type
L : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rating
100 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)
Fixed
[Ir] long-time protection pick-up adjustment range
1 x In
Long-time protection delay adjustment type tr
Fixed
Instantaneous protection pick-up adjustment type Ii
Fixed
[Ii] instantaneous protection pick-up adjustment range
800 A
earth-leakage protection
Without
Width (W)
70 mm
Height (H)
161 mm
Depth (D)
86 mm
Net weight
1.2 kg
standards
EN/IEC 60947
product certifications
CCC EAC Marine
Overvoltage category
Class II
Electrical shock protection class
Class II
Pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Relative humidity
0…95 %
Operating altitude
0...2000 m without derating 2000 m...5000 m with derating
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.000 cm
Package 1 Width
18.000 cm
Package 1 Length
13.000 cm
Package 1 Weight
1.281 kg
Warranty
18 months
Datasheet