C10R36E100

NSX100R 3P 200kA ML 6.2 E 100A

Trade Price

£2,193.57

Per

1

Unit

EA

Pack Quantity

1

C10R36E100

Information

This ComPacT NSX100R is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 200kA rms at 415VAC 50/60Hz and 45kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 100A rating electronic MicroLogic 6.2 E trip unit, with an adjustable ground-fault protection (with OFF position). MicroLogic 6.2 E trip unit provides adjustable long time, short time and instantaneous protection. MicroLogic 6.2 E has an embedded display unit for fine settings adjustment and display of the energy (energy meter). This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX100R is part of Schneider Electric EcoStruxure Power architecture.

Technical Specifications

Range

ComPacT new generation

Product name

ComPacT NSX new generation

Device short name

NSX100R

Product or component type

Circuit breaker

Device application

Distribution

Poles description

3P

Protected poles description

3D

[In] rated current

100 A at 40 °C

[Ue] rated operational voltage

690 V AC 50/60 Hz

Network type

AC

Network frequency

50/60 Hz

Suitability for isolation

Yes conforming to EN/IEC 60947-2

utilisation category

Category A

[Icu] rated ultimate short-circuit breaking capacity

200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

Performance level

R 200 kA 415 V AC

Trip unit name

MicroLogic 6.2 E

Trip unit technology

Electronic

Trip unit protection functions

LSIG

Control type

Toggle

Circuit breaker mounting mode

Fixed

[Ui] rated insulation voltage

800 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage

8 kV

[Ics] rated service short-circuit breaking capacity

200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability

20000 cycles

Electrical durability

20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In

Power dissipation per pole

4.7 W

mounting support

Backplate

Mounting position

Horizontal and vertical Flat on the back

Upside connection

Front

downside connection

Front

Connection pitch

35 mm

Protection type

L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection

Trip unit rating

100 A at 40 °C

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

40...100 A

Long-time protection delay adjustment type tr

Adjustable

[tr] long-time protection delay adjustment range

15…400 s at 1.5 x Ir 0.5…16 s at 6 x Ir 0.35…11 s at 7.2 x Ir

Thermal memory

20 minutes before and after tripping

Short-time protection pick-up adjustment type Isd

Adjustable

[Isd] Short-time protection pick-up adjustment range

1.5...10 x Ir

Short-time protection delay adjustment type tsd

Adjustable 5 settings

[tsd] Short-time protection delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

Instantaneous protection pick-up adjustment type Ii

Adjustable

[Ii] instantaneous protection pick-up adjustment range

1.5...15 x In

Ground-fault protection pick-up adjustment type Ig

Adjustable 9 settings

[Ig] ground-fault protection pick-up adjustment range

0.4...1 x In for In = 40 A 0.2...1 x In for In > 40 A Ig enable on/off

Ground-fault protection time delay adjustment type tg

Adjustable 5 settings

[tg] ground-fault protection time delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

earth-leakage protection

Without

Zone selective interlocking ZSI

With

Number of slots for electrical auxiliaries

5 slot(s)

Local signalling

Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload

Display type

LCD display

Type of measurement

Energy meter

communication of data

Maintenance indicators Energy metering Time-stamped histories and event tables Demand current and power Maximeters/minimeters Instantaneous and demand values Protection and alarm settings Power quality

Width (W)

105 mm

Height (H)

161 mm

Depth (D)

86 mm

Net weight

2.05 kg

standards

EN/IEC 60947

product certifications

Marine CCC EAC

Overvoltage category

Class II

Electrical shock protection class

Class II

Pollution degree

3 conforming to IEC 60664-1

IP degree of protection

IP40 conforming to IEC 60529

IK degree of protection

IK07 conforming to IEC 62262

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Relative humidity

0…95 %

Operating altitude

0...2000 m without derating 2000 m...5000 m with derating

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

20.000 cm

Package 1 Width

14.000 cm

Package 1 Length

11.000 cm

Package 1 Weight

1.950 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet