Trade Price
£2,972.94
Per
1
Unit
EA
Pack Quantity
1
This ComPacT NSX250HB2 is a complete 4P 4d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 100kA rms at 500VAC 50/60Hz and 100kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 250A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection. This 4 poles version (140mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX250HB2 is part of Schneider Electric EcoStruxure Power architecture.
Range
ComPacT new generation
Product name
ComPacT NSX new generation
Device short name
NSX250HB2
Product or component type
Circuit breaker
Device application
Distribution
Poles description
4P
Protected poles description
4D
Neutral position
Left
[In] rated current
250 A at 40 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
Network type
AC
Network frequency
50/60 Hz
Suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Performance level
HB2 100 kA 690 V AC
Trip unit name
TM-D
Trip unit technology
Thermal-magnetic
Trip unit protection functions
LI
Control type
Toggle
Circuit breaker mounting mode
Fixed
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ics] rated service short-circuit breaking capacity
100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability
20000 cycles
Electrical durability
20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Power dissipation per pole
18.75 W
mounting support
Backplate
Mounting position
Horizontal and vertical Flat on the back
Upside connection
Front
downside connection
Front
Connection pitch
35 mm
Protection type
L : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rating
250 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable
[Ir] long-time protection pick-up adjustment range
0.7...1 x In
Long-time protection delay adjustment type tr
Fixed
[tr] long-time protection delay adjustment range
120…400 s at 1.5 x In 15 s at 6 x Ir
Neutral protection settings
1 x Ir (4D)
Instantaneous protection pick-up adjustment type Ii
Adjustable
[Ii] instantaneous protection pick-up adjustment range
5...10 x In
earth-leakage protection
Without
Number of slots for electrical auxiliaries
5 slot(s)
Width (W)
140 mm
Height (H)
161 mm
Depth (D)
86 mm
Net weight
2.8 kg
standards
EN/IEC 60947
product certifications
CCC EAC Marine
Overvoltage category
Class II
Electrical shock protection class
Class II
Pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Relative humidity
0…95 %
Operating altitude
0...2000 m without derating 2000 m...5000 m with derating
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
14.0 cm
Package 1 Width
15.0 cm
Package 1 Length
20.0 cm
Package 1 Weight
2.723 kg
Unit Type of Package 2
S03
Number of Units in Package 2
3
Package 2 Height
30.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
8.169 kg
Warranty
18 months