C1032G100

NSX100-250 3P ML 2.2 G 100A TU

Trade Price

£327.88

Per

1

Unit

EA

Pack Quantity

1

C1032G100

Information

This MicroLogic 2.2 G is a 3 poles 3d electronic trip unit used on ComPacT NSX 100/160/250 circuit breakers. This 100A rating electronic trip unit is an optimum choice for generator protection applications. It embeds an adjustable long time protection against overloads. It provides also an adjustable short-time protection and a fixed instantaneous protection against short-circuits. MicroLogic 2.2 G indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and ComPacT NSX basic frame.

Technical Specifications

Range

ComPacT new generation

Range of produc

ComPacT NSX100...250 new generation

Product or component type

Trip unit

Trip unit name

MicroLogic 2.2 G

Trip unit technology

Electronic

Range compatibility

ComPacT new generation NSX100 ComPacT new generation NSX160 ComPacT new generation NSX250

Device application

Generator

Poles description

3P

Protected poles description

3D

Trip unit protection functions

LSoI

Protection type

L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection

Trip unit rating

100 A at 40 °C

[Ue] rated operational voltage

690 V AC 50/60 Hz

Network type

AC

Network frequency

50/60 Hz

Circuit breaker mounting mode

Fixed

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

40...100 A

Long-time protection delay adjustment type tr

Fixed

[tr] long-time protection delay adjustment range

15 s at 1.5 x Ir 0.35 s at 7.2 x Ir 0.5 s at 6 x Ir

thermal memory

20 minutes before and after tripping

Short-time protection pick-up adjustment type Isd

Adjustable

[Isd] Short-time protection pick-up adjustment range

1.5...9 x Ir

Short-time protection delay adjustment type tsd

Fixed

Instantaneous protection pick-up adjustment type Ii

Fixed

[Ii] instantaneous protection pick-up adjustment range

1500 A

earth-leakage protection

Without

Zone selective interlocking ZSI

Without

Local signalling

Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload

Standards

EN/IEC 60947-2

Electrical shock protection class

Class II

Pollution degree

3 conforming to IEC 60947-1

IP degree of protection

IP40 conforming to IEC 60529

ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-50…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

6.5 cm

Package 1 Width

9.5 cm

Package 1 Length

11.0 cm

Package 1 Weight

432.0 g

Unit Type of Package 2

S03

Number of Units in Package 2

24

Package 2 Height

30.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

10.828 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet