Trade Price
£2,604.92
Per
1
Unit
EA
Pack Quantity
1
VigiPacT RHB is a DIN rail mounting residual current protection and monitoring relay. It protects against people direct or indirect contact, property fire hazards and motors. It measures the earth leakage current in an electrical installation via its associated toroid. It trips the associated circuit breaker when the set residual operation current is overrun. It can activate an alarm and a pre-alarm. The operational supply voltage is 100/250VAC 50/400Hz or 100/250VDC. It is a type B earth-leakage protection class. The current sensitivity is adjustable from 30mA to 3A on the keypad. The time delay is adjustable on the keypad from instantaneous to 10s. The monitored distribution system voltage is up to 800 VAC 50/60/400 Hz. It is installed on a DIN-rail inside a switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type B toroid.
Range
VigiPacT
Device short name
RHB
Product or component type
Residual current protection relay
Relay application
Protection relay
Mounting support
DIN rail
Earth-leakage protection class
Type B
Type of setting
Keypad
Residual earth-leakage sensitity adjustment type
Adjustable
Earth-leakage sensitivity
0.03…0.1 A, adjustable in step of 0.001 A 0.1…1 A, adjustable in step of 0.01 A 1…3 A, adjustable in step of 0.1 A
Earth-leakage time delay
Instantaneous for 0.03 A Adjustable 0…1 s for 0.03…3 A adjustable in step of 10 ms Adjustable 1…10 s for 0.03…3 A adjustable in step of 100 ms
Threshold setting
0.015...1 A adjustable in step of 0.001 A alarm 1...3 A adjustable in step of 0.1 A alarm
Current sensors compatibility
VigiPacT TB35 earth leakage current sensor VigiPacT TB60 earth leakage current sensor VigiPacT TB120 earth leakage current sensor VigiPacT TB210 earth leakage current sensor VigiPacT TB35P earth leakage current sensor VigiPacT TB60P earth leakage current sensor
[Ithe] conventional enclosed thermal current
5 A
Minimum load
1 mA at 10 V
[Us] rated supply voltage
100...250 V AC 50...400 Hz 70...120 % 100...250 V DC
Power consumption in VA
6.5 VA
Monitored distribution system
800 V - AC at 0...2000 Hz (maximum)
Earthing system
TT TN-S
[Uimp] rated impulse withstand voltage
4 kV
Reset
Remote reset
Test function
Remote test Local
Monitoring
Electronics (watchdog) Power supply (continuous) Relay/sensor link (continuous)
Signal contacts composition
1 NO/NC alarm fail-safe 1 NO pre-alarm fail-safe
Type of measurement
Earth fault current internal measurement, range: 80...100 %
Tamperproof of settings
Protected by access code
Connections - terminals
Terminal block 1 cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12 Terminal block 1 cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12 Terminal block 2 cable(s) 0.2…1.5 mm² flexible AWG 24...AWG 12 Terminal block 2 cable(s) 0.2…1.5 mm² rigid AWG 24...AWG 12
Wire stripping length
8 mm 9 mm
Tightening torque
0.5…0.6 N.m
9 mm pitches
4
Width
36 mm
Height
90 mm
Depth
70.5 mm
Net weight
0.15 kg
IP degree of protection
IP40 on front face: conforming to EN/IEC 60529 IP30 on side parts: conforming to EN/IEC 60529 IP20 on connection terminals: conforming to EN/IEC 60529
IK degree of protection
IK07 conforming to EN 50102
Mechanical robustness
Fire resistance conforming to IEC 60695-2-1 IK protection 2 joules: IK07 conforming to EN 50102 Vibrations 13.2...100 Hz: 0.7 g Vibrations 2...13.2 Hz: +/- 1 mm
Environmental characteristic
Exposure to damp heat not in service conforming to IEC 60068-2-30 Exposure to damp heat in service conforming to IEC 60068-2-56 Salt mist conforming to IEC 60068-2-52
Overvoltage category
III
Electrical shock protection class
Class II
Electromagnetic compatibility
Conducted and radiated emissions: , B, conforming to CISPR 11 Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6 Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2 High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5 Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4 Radiated susceptibility: , 3, conforming to IEC 61000-4-3
Relative humidity
95 % at 55 °C
Pollution degree
2 conforming to IEC 60664-1
Ambient air temperature for operation
-25…55 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
5.3 cm
Package 1 Width
12.0 cm
Package 1 Length
16.0 cm
Package 1 Weight
238.0 g
Unit Type of Package 2
S04
Number of Units in Package 2
40
Package 2 Height
30 cm
Package 2 Width
40 cm
Package 2 Length
60 cm
Package 2 Weight
10.25 kg
Warranty
18 months