Trade Price
£80.82
Per
1
Unit
EA
Pack Quantity
1
This current transformer, tropicalised for busbar and cable, has a line rated current of 400 A and a secondary current rating of 5 A. This current transformer allow a maximum cable outer diameter of 26 mm. Compatible with a double output for bar: 40.5 mm x 12.5 mm or 32.5 mm x 15.5 mm. Burden and accuracy class as follows: class 0.5 maximum power: 6 VA, class 1 maximum power: 8 VA.
Range
PowerLogic
Product name
CT
Product or component type
Current transformer
Secondary current
5 A
Accuracy class
Class 0.5 at 6 VA Class 1 at 8 VA
[In] rated current
400 A
current transformer type
Tropicalised for busbar and cable
current transformer ratio
400/5
[Ith] conventional free air thermal current
24 kA
dynamic withstand current
2.5 Ith
Maximum safety factor
5
[Ue] rated operational voltage
< 720 V AC 50/60 Hz
[Ui] rated insulation voltage
3 kV
Mounting mode
Insulated locking screw By screws Clip-on
mounting support
Mounting plate Busbar DIN rail
Width
60 mm outside:
Height
85 mm outside:
Depth
43 mm frame: 63 mm total:
Diameter
26 mm
Net weight
0.348 kg
[Uimp] rated impulse withstand voltage
3 kV
Electrical insulation class
Class B
Cable outer diameter
26 mm
Opening of bars
40.5 x 12.5 32.5 x 15.5
Sealing
Without
standards
IEC 61869-2 VDE 0414
product certifications
CE
IP degree of protection
IP20
Relative humidity
0…95 %
Ambient air temperature for operation
-25…60 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.2 cm
Package 1 Width
7.0 cm
Package 1 Length
9.2 cm
Package 1 Weight
334.0 g
Unit Type of Package 2
S03
Number of Units in Package 2
55
Package 2 Height
30.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
19.022 kg
Warranty
18 months