K30F003UP

32 AMPS CAM SWITCH

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

K30F003UP
K30F003UP
K30F003UP
K30F003UP

Information

This Harmony K30 complete cam switch/selector switch has 3 poles (3P). It also has a rating of 32A, a screw clamp mounting mode and a metallic color with black marking. It has '1 - 0 - 2' marking to indicate the position of the switch. This metal head complete cam switch/selector switch is designed to meet most industrial and process control application thanks to a compact size, an easy integration with 16mm and 22mm diameter units and has several selection functions. It has a 60 degree between its switching positions.

Technical Specifications

Range of produc

Harmony K

Product or component type

Complete cam switch

component name

K30

[Ith] conventional free air thermal current

32 A

Mounting location

Front

Fixing mode

4 holes

Cam switch head type

With front plate 64 x 64 mm

Type of operator

Black handle

Rotary handle padlocking

Without

Presentation of legend

With metallic legend, 1 - 0 - 2 black marking

Cam switch function

Changeover switch

Return

Without

Off position

With Off position

Poles description

3P

Switching positions

Right: 0° - 60° Left: 0° - 300°

IP degree of protection

IP40 conforming to IEC 60529

Switching angle

60 °

[Ui] rated insulation voltage

690 V (pollution degree 3) conforming to IEC 60947-1

Short-circuit current

5000 A

Short-circuit protection

50 A cartridge fuse, type gG

[Uimp] rated impulse withstand voltage

6 kV conforming to EN 947-1 6 kV conforming to IEC 947-1

contact operation

Slow-break

Positive opening

With

Electrical connection

Captive screw clamp terminals flexible, clamping capacity: 2 x 4 mm² Captive screw clamp terminals solid, clamping capacity: 2 x 6 mm²

Tightening torque

1.2 N.m

Switching capacity in mA

11000 mA DC at 120 V 2 contact(s) for inductive load (T = 50 ms) 11000 mA DC at 180 V 3 contact(s) for inductive load (T = 50 ms) 11000 mA DC at 60 V 1 contact(s) for inductive load (T = 50 ms) 1200 mA DC at 220 V 1 contact(s) for resistive load (T = 1 ms) 1200 mA DC at 440 V 2 contact(s) for resistive load (T = 1 ms) 1200 mA DC at 660 V 3 contact(s) for resistive load (T = 1 ms) 16000 mA DC at 140 V 3 contact(s) for inductive load (T = 50 ms) 16000 mA DC at 48 V 1 contact(s) for inductive load (T = 50 ms) 16000 mA DC at 95 V 2 contact(s) for inductive load (T = 50 ms) 23000 mA DC at 120 V 2 contact(s) for resistive load (T = 1 ms) 23000 mA DC at 180 V 3 contact(s) for resistive load (T = 1 ms) 23000 mA DC at 60 V 1 contact(s) for resistive load (T = 1 ms) 25000 mA DC at 30 V 1 contact(s) for inductive load (T = 50 ms) 25000 mA DC at 60 V 2 contact(s) for inductive load (T = 50 ms) 25000 mA DC at 90 V 3 contact(s) for inductive load (T = 50 ms) 3200 mA DC at 110 V 1 contact(s) for inductive load (T = 50 ms) 3200 mA DC at 220 V 2 contact(s) for inductive load (T = 50 ms) 3200 mA DC at 330 V 3 contact(s) for inductive load (T = 50 ms) 32000 mA DC at 140 V 3 contact(s) for resistive load (T = 1 ms) 32000 mA DC at 24 V 1 contact(s) for inductive load (T = 50 ms) 32000 mA DC at 24 V 1 contact(s) for resistive load (T = 1 ms) 32000 mA DC at 48 V 1 contact(s) for resistive load (T = 1 ms) 32000 mA DC at 48 V 2 contact(s) for inductive load (T = 50 ms) 32000 mA DC at 48 V 2 contact(s) for resistive load (T = 1 ms) 32000 mA DC at 70 V 3 contact(s) for inductive load (T = 50 ms) 32000 mA DC at 70 V 3 contact(s) for resistive load (T = 1 ms) 32000 mA DC at 95 V 2 contact(s) for resistive load (T = 1 ms) 400 mA DC at 440 V 1 contact(s) for resistive load (T = 1 ms) 400 mA DC at 660 V 2 contact(s) for resistive load (T = 1 ms) 6500 mA DC at 110 V 1 contact(s) for resistive load (T = 1 ms) 6500 mA DC at 220 V 2 contact(s) for resistive load (T = 1 ms) 6500 mA DC at 330 V 3 contact(s) for resistive load (T = 1 ms)

Mechanical durability

300000 cycles

CAD overall width

64 mm

CAD overall height

64 mm

CAD overall depth

106 mm

Net weight

0.425 kg

Standards

IEC 60947-3

Product certifications

CULus 120 V 2 hp 1 phase CULus 240 V 5 hp 1 phase CULus 240 V 5 hp 3 phases CULus 480 V 20 hp 3 phases

Protective treatment

TC

ambient air temperature for operation

-25…55 °C

Ambient air temperature for storage

-40…70 °C

Overvoltage category

Class II conforming to IEC 60536 Class II conforming to NF C 20-030

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

7.4 cm

Package 1 Width

7.5 cm

Package 1 Length

12.0 cm

Package 1 Weight

281.0 g

Unit Type of Package 2

S03

Number of Units in Package 2

30

Package 2 Height

30.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

8.963 kg

Warranty

18 months

Document Links