KSB50SF5

TAP OFF UNIT 50A FUSE 14X51

Trade Price

POA

Per

1

Unit

Pack Quantity

KSB50SF5

Information

Canalis tap-off unit for KT and KS. It's applied to medium power distribution and TN-C earthing system. The operational voltage is from 230VAC 50/60Hz to 690VAC 50/60Hz. The rated operational current is 50A at 35 ℃. Mounting by Plug-in with fixed polarity with white RAL 9001 surface treatment and whose busbar trunking polarity is 3L+PEN. It provided protection for size 14 x 51 fuses (Fuse to be ordered separately). It provided tap-off unit disconnection by right opening the door. Canalis KS busbar trunking compatibility with plug-in outlets, Canalis KT busbar trunking compatibility with KS type plug-in outlets. It provides IP55 protection which conforming to IEC 60529 standard. IK08 conforms to IEC 62262. It is compliant with both IEC 61439-1 and IEC 61439-6. It is also compliant with Green Premium (RoHS/REACH).

Technical Specifications

Range of product

Canalis

Range compatibility

Canalis (KT) busbar trunking Canalis (KS) busbar trunking

Product or component type

Tap-off unit

busbar trunking compatibility

Canalis KS busbar trunkingplug-in Canalis KT busbar trunking with KS type plug-in

[Ie] rated operational current

50 A at 35 °C

protection type

fuse isolator: for aM cylindrical fuse, size 14 x 51 mm - 50 A conforming to NF fuse isolator: for gG cylindrical fuse, size 14 x 51 mm - 50 A conforming to NF

Provided equipment

fuse to be ordered separately

Mounting mode

Plug-in with fixed polarity

Tap-off unit polarity

3L+PEN

Colour

White (RAL 9001)

Device application

Medium power distribution

[Ue] rated operational voltage

230...690 V depending on protective device

[Uimp] rated impulse withstand voltage

6.8 kV

[Ui] rated insulation voltage

500 V depending on protective device

Network frequency

50/60 Hz

Electrical connection

Cable clamp terminal - ISO50 25 mm² flexible Cable clamp terminal - ISO50 25 mm² rigid

door/cover opening side

Right

Tap-off unit disconnection mode

By opening the door

Standards

IEC 61439-1 IEC 61439-6

body material

Plastic

Width

356 mm

Depth

103 mm

depth (door open)

432.5 mm

height

202 mm

Net weight

2.4 kg

Earthing system

TN-C

IP degree of protection

IP55 conforming to IEC 60529

IK degree of protection

IK08 conforming to IEC 62262

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

16.700 cm

Package 1 Width

22.500 cm

Package 1 Length

35.800 cm

Package 1 Weight

2.142 kg

Unit Type of Package 2

P12

Number of Units in Package 2

38

Package 2 Height

80.000 cm

Package 2 Width

80.000 cm

Package 2 Length

120.000 cm

Package 2 Weight

105.000 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet