Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1
Altivar Soft Starter ATS480 is intended to start and stop asynchronous motors supplied from 208V to 690V. It meets the requirements of the most demanding applications in normal and heavy duty. With an operational rated current of 88A in normal duty, it supplies motor from 22kW to 75kW according to mains voltage. Designed for digitization, connected, optimized to meet cybersecurity standard, it simplifies project execution and maximizes the availability of applications. Its torque control (TCS) masters acceleration and deceleration. It efficiently stops high inertia application thanks to the dynamic braking and DC injection. It could be connected in-line or inside the delta to reduce its operational current. The embedded test routine simplifies the commissioning inside the delta. Its dimensions are 190mm (width) x 247mm (depth) x 290mm (height) and it weighs 8,3kg. Altivar Soft Starter ATS480 is designed to address process, infrastructures and industrial machines. It conforms to IEC/EN60947-4-1. It is certified CE, cULus, UKCA, CCC, RCM, EAC, and Marine certified DNV, ABS, BV and CCS. Display terminals, remote mounting kit, communication modules are common with Altivar Drives. Line chokes, DNV kits are common with ATS48. ATS480 is compatible with ATS48, it has same footprint, fixing, torque control algorithm, I/O, menus… The integration of Altivar Soft Starter ATS480 in EcoStruxure drastically simplifies architecture selection, detailed design and execution in automation and electrical systems. It is a Green Premium product designed to take the environmental considerations beyond current directives and regulations, compliant with RoHS and REACH.
Range of product
Altivar Soft Starter ATS480
Product or component type
Soft starter
Product destination
Asynchronous motors
Product specific application
Process and infrastructures
Device short name
ATS480
Network number of phases
3 phases
utilisation category
AC-3A AC-53A
Ue power supply voltage
208...690 V - 15...10 %
power supply frequency
50...60 Hz - 20...20 %
[Ie] rated operational current
Normal duty: 88.0 A (at <40 °C)
rated current in heavy duty
75.0 A at 40 °C for heavy duty
Torque control
True
IP degree of protection
IP20
Motor power kW
22.0 kW at 230 V in the motor supply line normal duty 18.5 kW at 230 V in the motor supply line heavy duty 45.0 kW at 400 V in the motor supply line normal duty 37.0 kW at 400 V in the motor supply line heavy duty 45.0 kW at 440 V in the motor supply line normal duty 37.0 kW at 440 V in the motor supply line heavy duty 55.0 kW at 500 V in the motor supply line normal duty 45.0 kW at 500 V in the motor supply line heavy duty 55.0 kW at 525 V in the motor supply line normal duty 45.0 kW at 525 V in the motor supply line heavy duty 75.0 kW at 660 V in the motor supply line normal duty 55.0 kW at 660 V in the motor supply line heavy duty 75.0 kW at 690 V in the motor supply line normal duty 55.0 kW at 690 V in the motor supply line heavy duty 45.0 kW at 230 V to the motor delta terminals normal duty 37.0 kW at 230 V to the motor delta terminals heavy duty 75.0 kW at 400 V to the motor delta terminals normal duty 55.0 kW at 400 V to the motor delta terminals heavy duty
Motor power hp
25.0 hp at 208 V normal duty 20.0 hp at 208 V heavy duty 30.0 hp at 230 V normal duty 25.0 hp at 230 V heavy duty 60.0 hp at 460 V normal duty 50.0 hp at 460 V heavy duty 75.0 hp at 575 V normal duty 60.0 hp at 575 V heavy duty
Option card
Communication module for Profibus DP V1 Communication module for PROFINET Communication module for Modbus TCP/EtherNet/IP Communication module for CANopen daisy chain Communication module for CANopen Sub-D Communication module for CANopen open style
device connection
In the motor supply line To the motor delta terminals
[Us] control circuit voltage
110...250 V AC 50/60 Hz - 15...10 %
Apparent power
0.09 kVA
Integrated motor overload protection
True
motor thermal protection class
Class 10E
Protection type
Phase failure: line Integrated thermal protection: motor Thermal protection: starter Current overload: motor Underload: motor Excessive starting time, locked rotor: motor Motor phase loss: motor Line supply phase loss: line Line supply phase loss: motor Thermal protection: motor
current limiting %In (5 x Ie maximum)
150…700 %
Rated current pwr loss specification
88.0 A
Power loss static current independent
25.0 W
Power loss per device current dependent
270.0 W
standards
IEC 60947-4-2 UL 60947-4-2 IEC 60664-1
product certifications
CE cULus CCC UKCA RCM EAC DNV ABS BV CCS
Marking
CE CCC UKCA EAC RCM CULus
[Uc] control circuit voltage
24 V DC
Discrete input number
4
Discrete input type
(STOP) logic inputs, 3500 Ohm (RUN) logic inputs, 3500 Ohm (DI3) programmable as logic input, 3500 Ohm (DI4) programmable as logic input, 3500 Ohm
Input compatibility
STOP: discrete input level 1 PLC conforming to IEC 61131-2 RUN: discrete input level 1 PLC conforming to IEC 61131-2 DI3: discrete input level 1 PLC conforming to IEC 61131-2 DI4: discrete input level 1 PLC conforming to IEC 61131-2
Discrete input logic
Programmable digital input at State 0: < 5 V
Relay output number
3
Relay output type
Relay outputs R1A 1 NO Relay outputs R1B 1 NO Relay outputs RIC NO/NC programmable
Minimum switching current
100 mA at 12 V DC for relay outputs
Maximum switching current
Relay outputs 2 A at 250 V AC Relay outputs 2 A at 30 V DC Relay outputs
Discrete output number
2
Discrete output type
(DQ1) programmable digital output <= 30 V (DQ2) programmable digital output <= 30 V
Output compatibility
Open collector level 1 PLC conforming to IEC 65A-68
analogue input number
1
Analogue input type
AI1/PTC PTC/Pt 100 temperature probe PTC2 PTC/Pt 100 temperature probe PTC3 PTC/Pt 100 temperature probe
analogue output number
1
Analogue output type
Current output AQ1: 0...20 mA or 0...10 V, impedance <500 Ohm
Communication port protocol
Modbus serial
Connector type
1 RJ45
Communication data link
Serial
Physical interface
2-wire RS 485
Transmission rate
1200...256000 bit/s
Transmission frame
RTU
Data format
8 bits, configurable odd, even or no parity
Type of polarization
No impedance for Modbus serial
Number of addresses
0…227 for Modbus serial
Method of access
Slave Modbus serial
Function available
External bypass control Pre-heating Smoke extraction Multi-motor cascade Second motor set User management Ports and services hardening Security event logging Cybersecure firmware update Single direction
Display screen available
True
Operating position
Vertical +/- 10 degree
height
290.0 mm
Width
190.0 mm
Depth
247.0 mm
Net weight
8.3 kg
Electromagnetic compatibility
Conducted and radiated emissions level A conforming to IEC 60947-4-2 Conducted and radiated emissions with bypass level B conforming to IEC 60947-4-2 Damped oscillating waves level 3 conforming to IEC 61000-4-12 Electrostatic discharge level 3 conforming to IEC 61000-4-11 Immunity to electrical transients level 4 conforming to IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3 Voltage/current impulse level 3 conforming to IEC 61000-4-5
Pollution degree
Level 3
[Uimp] rated impulse withstand voltage
6 kV
[Ui] rated insulation voltage
690 V
Environmental class (during operation)
Class 3C3 according to IEC 60721-3-3 Class 3S2 according to IEC 60721-3-3
Relative humidity
0…95 % without condensation or dripping water conforming to IEC 60068-2-3
Ambient air temperature for operation
40…60 °C (with current derating of 2 % per °C) -15…40 °C (without derating)
Ambient air temperature for storage
-25…70 °C
Operating altitude
<= 1000 m without derating > 1000...4000 m with current derating 1 % per 100 m
Maximum deflection under vibratory load (during operation)
1.5 mm at 2...13 Hz
Maximum deflection under vibratory load (during storage)
1.75 mm at 2...9 Hz
Maximum deflection under vibratory load (during transport)
1.75 mm at 2...9 Hz
Maximum acceleration under vibrational stress (during operation)
10 m/s² at 13...200 Hz
Maximum acceleration under vibratory load (during storage)
15 m/s² at 200...500 Hz 10 m/s² at 9...200 Hz
Maximum acceleration under vibratory load (during transport)
15 m/s² at 200...500 Hz 10 m/s² at 9...200 Hz
Maximum acceleration under shock impact (during operation)
150 m/s² at 11 ms
Maximum acceleration under shock load (during storage)
100 m/s² at 11 ms
Maximum acceleration under shock load (during transport)
100 m/s² at 11 ms
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
37.000 cm
Package 1 Width
31.000 cm
Package 1 Length
39.000 cm
Package 1 Weight
9.785 kg
Unit Type of Package 2
P06
Number of Units in Package 2
8
Package 2 Height
86.000 cm
Package 2 Width
60.000 cm
Package 2 Length
80.000 cm
Package 2 Weight
86.500 kg
Warranty
18 months
Datasheet