Trade Price
£545.59
Per
1
Unit
EA
Pack Quantity
1
This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to 15th Harmonic. Include a non-volatile memory for several parameters and alarms. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 85 to 265 VAC and 100 to 300 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 20V AC to 480V AC, CAT III or 20V AC to 690V AC, CAT II at 45 Hz to 70 Hz. The range of measurement voltage between Phase and Neutral is 20V AC to 277V AC, CAT III or 20V AC to 400V AC, CAT II at 45 Hz to 70 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has four digital inputs and dual relay outputs. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.24 inches (57 millimetres), height 3.78 inches (96 millimetres) and product weight 8.8 onces (250 g).
Range
PowerLogic
Product name
PowerLogic PM5350
Device short name
PM5350
Product or component type
Power meter
Power quality analysis
total demand distortion total harmonic distortion
Device application
Power monitoring
Type of measurement
Current Voltage Frequency Power factor Energy Phase angle Apparent power Active power Reactive power
supply voltage
85...265 V AC 45...65 Hz 100...300 V DC
Network frequency
50 Hz 60 Hz
[In] rated current
5 A 1 A
type of network
1P + N 3P + N 3P
Maximum power consumption in VA
11.9 VA
Ride-through time
100 ms 120 V AC typical 400 ms 230 V AC typical 50 ms 125 V DC typical
Display type
Monochrome graphic LCD
Display resolution
6 lines
Sampling rate
32 samples/cycle
Measurement current
5…9000 mA
Analogue input type
Current 0.05...9 A (impedance <= 0.3 mOhm) Voltage (impedance 10 MOhm)
Measurement voltage
35…480 V AC 45...65 Hz phase to phase 20…277 V AC phase to neutral
Frequency measurement range
45…70 Hz
Number of inputs
4 digital
Measurement accuracy
Current +/- 0.3 % Voltage +/- 0.3 % Frequency +/- 0.05 % Power factor +/- 0.005 Active energy +/- 0.5 % Reactive energy +/- 2 % Active power +/- 0.5 % Apparent power +/- 0.5 % Apparent energy +/- 0.5 % Reactive power +/- 2 %
Accuracy class
Class 0.5S active energy conforming to IEC 62053-22 Class 0.5 active energy conforming to IEC 61557-12 Class 2 reactive energy conforming to IEC 62053-23 Class 2 reactive energy conforming to IEC 61557-12 Class 0.5 power conforming to IEC 61557-12
Number of outputs
2 relay
Information displayed
Tariff (4)
Communication port protocol
JBUS Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds
Communication port support
Terminal block: RS485
data recording
Min/max of instantaneous values Alarms
Connections - terminals
Voltage circuit: screw terminal block4 Control circuit: screw terminal block2 Current transformer: screw terminal block6 Input/output circuit: screw terminal block6 Relay output: screw terminal block4 Ethernet network: RJ45 connector
Mounting mode
Flush-mounted
Type of installation
Indoor installation
Standards
IEC 61010-1
Product certifications
CE CULus
Width
96 mm
Depth
44 mm
Height
96 mm
Net weight
0.25 kg
Electromagnetic compatibility
Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3 Electrostatic discharge conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 Conducted RF disturbances conforming to IEC 61000-4-6 Immunity to impulse waves conforming to IEC 61000-4-12 Conducted and radiated emissions class A conforming to EN 55011 Limits for harmonic current emissions conforming to IEC 61000-3-2
Overvoltage category
III
IP degree of protection
IP30 rear: conforming to IEC 60529 IP54 display: conforming to IEC 60529
Relative humidity
5…95 % at 50 °C non-condensing
Pollution degree
2
Ambient air temperature for operation
-25…70 °C meter -20…70 °C display -25…-20 °C (with reduced performance) display
Ambient air temperature for storage
-40…85 °C
Operating altitude
<= 3000 m
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
11.200 cm
Package 1 Width
12.500 cm
Package 1 Length
12.700 cm
Package 1 Weight
346.000 g
Unit Type of Package 2
S03
Number of Units in Package 2
12
Package 2 Height
30.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
4.962 kg
Warranty
18 months
Datasheet