Trade Price
£46.72
Per
1
Unit
EA
Pack Quantity
1
This Acti9 electrical auxiliary is a modular fault contact used as remote indication of tripping upon a fault of the associated device. The rated current (In) is from 2mA to 100mA with operating frequency of 50Hz to 60Hz at 24VAC to 250VAC, and from 2mA to 100mA at 24VDC to 220VDC. It has 1 position switch with contacts type 1 C/O. It is intended for new or renovated installation in small commercial, buildings, critical buildings, healthcare, industry, data center and infrastructures. This fault contact is compatible with Acti9 ranges such as C120, C60H-DC, SW60-DC and C60PV-DC. The SD is either used for device short name or compatibility code. The mechanical indicator is provided on the product for signalling (Local). It has a screw clamp terminal connection at bottom. The connection allows rigid copper cable. The cable cross section capacity is from 1mm² to 4mm². It has a screw clamp terminal connection at bottom. The connection allows flexible copper cable. The cable cross section capacity is from 0.5mm² to 2.5mm². It has a screw clamp terminal connection at bottom. The connection allows rigid copper cables (2 cables). The cable cross section capacity is 2.5mm². It has a screw clamp terminal connection at bottom. The connection allows flexible with ferrule copper cables (2 cables). The cable cross section capacity is 1.5mm². The rated insulation voltage (Ui) is up to 500V. It has a rated impulse withstand voltage (Uimp) of 4kV. The width in 9mm pitches is 1. The dimensions are (W) 9mm x (H) 86mm x (D) 73mm. The product colour is white (RAL 9003). The pollution degree is 3. The level of tropicalisation is treatment 2. The tightening torque of connection is 1N.m (bottom) for PZ1 screwdriver type. According to IEC 60529 standard, the IP degree of protection is IP20. The operating temperature is from -25°C to +70°C. The storage temperature is from -40°C to +85°C. This product complies with EN/IEC 60947-5-1 and EN/IEC 60947-5-4 standards. This product is certified with CE and UKCA standards.
range of product
Acti9
Product or component type
Fault contact
Device short name
SD
Signal contacts composition
1 C/O
[In] rated current
2…100 mA at 24...240 V, AC 50/60 Hz 2…100 mA at 24 V, DC 2…100 mA at 48 V, DC 2…100 mA at 60 V, DC 2…100 mA at 130 V, DC 2…100 mA at 220 V, DC
9 mm pitches
1
Operating mode
Daisy chain up to 100 devices
[Ui] rated insulation voltage
500 V
[Uimp] rated impulse withstand voltage
4 kV
Local signalling
Mechanical indicator
Mounting mode
Clip-on
Mounting location
Left side of circuit-breaker
mounting support
DIN rail
Comb busbar and distribution block compatibility
Top: YES
height
85.3 mm
Width
9 mm
Depth
68 mm
Net weight
30 g
Colour
White
Connections - terminals
Screw clamp terminal (bottom) 1 cable(s) 0.5…2.5 mm² - rigid Screw clamp terminal (bottom) 2 cable(s) 1.5 mm² - flexible Screw clamp terminal (bottom) 2 cable(s) 1.5 mm² - flexible with ferrule
Wire stripping length
9 mm
Tightening torque
1 N.m bottom
standards
EN/IEC 60947-5-1 EN/IEC 60947-5-4 GB/T 14048.5 GB/T 14048.17
product certifications
CE UKCA
Quality labels
EAC CCC
IP degree of protection
IP20
Pollution degree
3
Tropicalisation
2
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
1.8 cm
Package 1 Width
7.6 cm
Package 1 Length
9.3 cm
Package 1 Weight
38.8 g
Unit Type of Package 2
BB1
Number of Units in Package 2
12
Package 2 Height
8.7 cm
Package 2 Width
10 cm
Package 2 Length
23.4 cm
Package 2 Weight
522 g
Unit Type of Package 3
S03
Number of Units in Package 3
120
Package 3 Height
26.9 cm
Package 3 Width
28.5 cm
Package 3 Length
38.7 cm
Package 3 Weight
6 kg
Warranty
18 months