A9TDFD616

MCB+RCD+AFD 16A 30 mA A SI C 1P+N

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

A9TDFD616

Information

This Acti9 Active iCV40 ARC product is an arc fault detection RCBO. It is a 1P+N with 1 protected pole, 16A In rated current and C tripping curve. The earth leakage protection class is A-SI type with a sensitivity of 30mA. The earth-leakage protection time delay is instantaneous. The rated short circuit breaking capacity goes up to 10000A at 230VAC conforming to EN/IEC 61009-2-1 standard and 10kA at 230VAC conforming to EN/IEC60947-2. This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards. The Acti9 Active products communicate with the gateway EcoStruxure Panel Server Entry, Universal and Advanced. Its pre alarming system can prevent any overload, earth leakage and overvoltage. It can also measure the voltage, the current and the power. Its 2 unique VisiTrip indicators reduce intervention time by showing the faulty circuit and identifying quickly the type of default. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ui rated insulation voltage is 250VAC. Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 2. The product colour is white (RAL9003). The dimensions are (W) 36mm x (H) 91mm x (D)73mm. It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure. This product is compliant with EN/IEC 60898-1, EN/IEC 60947-2, EN/IEC 62606, EN/IEC 61009-1 and EN/IEC 61009-2-1 standard.

Technical Specifications

Range

Acti9

Product name

Acti9 iCV40 ARC

Product or component type

Arc fault detection RCBO

Product specific application

Arc fault detection

standards

EN/IEC 62606 EN/IEC 61009-1 EN/IEC 60947-2 EN/IEC 61009-2-1 BS EN 62606

Device short name

iCV40 ARC

Poles description

1P + N

Number of protected poles

1

Curve code

C

Breaking capacity

10000 A Icn at 230 V AC 50 Hz conforming to IEC 61009-2-1 10 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2

Rated breaking and making capacity

Idm 3000 A at 230 V AC 50 Hz conforming to IEC 61009-2-1

Neutral position

Left

Network type

AC

earth-leakage protection time delay

Instantaneous

Earth-leakage protection class

Type A-SI (Super Immunised)

electrical data recording

Date and time Maintenance indicators

Concentrator compatibility

EcoStruxure Panel Server Advanced EcoStruxure Panel Server Entry EcoStruxure Panel Server Universal

Event management

Overvoltage Earth leakage Overload

Type of measurement

Voltage Active power Current Power factor

Accuracy

Voltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %

Suitability for isolation

Yes

Residual current tripping technology

Voltage independent

Trip unit technology

Thermal-magnetic

earth-leakage protection

Integrated

[In] rated current

16 A

Network frequency

50 Hz

[Ue] rated operational voltage

230 V AC 50 Hz

device location in system

Outgoer

Magnetic tripping limit

5...10 x In

[Ics] rated service breaking capacity

7500 A AC 50 Hz conforming to IEC 61009-2-1 7.5 kA AC 50 Hz conforming to IEC 60947

Limitation class

3

[Ui] rated insulation voltage

250 V AC 50 Hz between phase and neutral

Threshold tripping voltage

275 V for +/- 5 V

[Uimp] rated impulse withstand voltage

4 kV

Contact position indicator

Yes

Control type

Toggle

Local signalling

ON, OFF, fault trip LED arc fault diagnostic

Mounting mode

Clip-on

mounting support

DIN rail

Colour

White (RAL 9003)

Mechanical durability

20000 cycles

Electrical durability

20000 cycles 230 V AC 50 Hz

Overvoltage category

III

Locking options description

Padlocking device

Cable entry

Top and bottom

Connections - terminals

Tunnel type terminal 1…16 mm² rigid Tunnel type terminal 1…10 mm² flexible

Wire stripping length

14 mm

Tightening torque

2 N.m

Comb busbar and distribution block compatibility

YES

9 mm pitches

4

height

91 mm

Width

36 mm

Depth

73 mm

Net weight

220 g

Earth-leakage sensitivity

30 mA

IP degree of protection

IP20 conforming to IEC 60529

Pollution degree

2 conforming to EN/IEC 62606

Tropicalisation

Severity B conforming to IEC 60068-2-30 for 28 d

Relative humidity

95 % at 55 °C

Operating altitude

2000 m

Ambient air temperature for operation

-25…40 °C

Ambient air temperature for storage

-40…80 °C

product certifications

UKCA

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

4.4 cm

Package 1 Width

8.5 cm

Package 1 Length

11.4 cm

Package 1 Weight

240.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

24

Package 2 Height

15.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

6.067 kg

Warranty

18 months

Document Links

Datasheet