LV430629

160A 3P NSX160NA

Trade Price

£453.97

Per

1

Unit

EA

Pack Quantity

1

LV430629

Information

This Compact NSX160NA is a complete 3 poles switch disconnector. It is used to control and isolate electrical distribution circuits and it requires an upstream protection. The operational current is 160A at 415VAC 50/60Hz for AC22A and AC23A utilization categories. The operational voltage is 690VAC 50/60Hz. It comes with a variety of optional functions and accessories common with Compact NSX circuit breakers. The dimensions for this 3 poles version are 105mm x 161mm x 86mm. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications.

Technical Specifications

Range

ComPact

Product name

ComPact NSX

Product or component type

Switch disconnector

Device short name

Compact NSX160NA

Poles description

3P

Network type

DC AC

[Ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-3 750 V DC 3 poles in series conforming to IEC 60947-3 500 V DC 2 poles in series conforming to IEC 60947-3 250 V DC 1 pole conforming to IEC 60947-3

[Ie] rated operational current

AC-22A: 160 A AC 50/60 Hz 220...690 V AC-23A: 160 A AC 50/60 Hz 220...690 V DC-22A: 160 A DC 250 V 1 pole DC-22A: 160 A DC 500 V 2 poles in series DC-23A: 160 A DC 250 V 1 pole DC-23A: 160 A DC 500 V 2 poles in series

[Ui] rated insulation voltage

800 V AC 50/60 Hz conforming to IEC 60947-3

[Uimp] rated impulse withstand voltage

8 kV conforming to IEC 60947-3

[Ith] conventional free air thermal current

160 A at 60 °C

[Icm] rated short-circuit making capacity

330 kA with upstream protection circuit breaker 3.6 kA switch-disconnector alone

Breaking capacity code

NA

Suitability for isolation

Yes conforming to EN 60947-3 Yes conforming to IEC 60947-3

Contact position indicator

Yes

Visible break

No

Pollution degree

3 conforming to IEC 60664-1

control type

Toggle

Mounting mode

Fixed

mounting support

Backplate

Upside connection

Front

downside connection

Front

[Icw] rated short-time withstand current

0.96 kA during 20 s conforming to IEC 60947-3 2.5 kA during 1 s conforming to IEC 60947-3 2.5 kA during 3 s conforming to IEC 60947-3

Mechanical durability

40000 cycles conforming to IEC 60947-3

Electrical durability

AC-22A: 10000 cycles 250 V DC In/2 (1 pole) conforming to IEC 60947-3 AC-22A: 5000 cycles 500 V DC In (2 poles in series) conforming to IEC 60947-3 AC-23A: 10000 cycles 250 V DC In/2 (1 pole) conforming to IEC 60947-3 AC-23A: 5000 cycles 500 V DC In (2 poles in series) conforming to IEC 60947-3 AC-22A: 10000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-3 AC-22A: 15000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-3 AC-22A: 30000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-3 AC-22A: 5000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-3 AC-23A: 10000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-3 AC-23A: 15000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-3 AC-23A: 30000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-3 AC-23A: 5000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-3

Connection pitch

35 mm

height

161 mm

Width

105 mm

Depth

86 mm

Net weight

1.8 kg

Standards

EN/IEC 60947 UL 508

product certifications

EAC CCC

IP degree of protection

IP40 conforming to IEC 60529

IK degree of protection

IK07 conforming to IEC 62262

Electrical shock protection class

Class II

ambient air temperature for operation

-35…70 °C

Ambient air temperature for storage

-55…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

13.8 cm

Package 1 Width

11.5 cm

Package 1 Length

19.2 cm

Package 1 Weight

1.865 kg

Unit Type of Package 2

S04

Number of Units in Package 2

12

Package 2 Height

30.0 cm

Package 2 Width

40.0 cm

Package 2 Length

60.0 cm

Package 2 Weight

23.386 kg

Warranty

18 months

Document Links

Datasheet