DVR60040400S

600KVA 400V DVR 40 Perc Sag Slave

Trade Price

£84,185.36

Per

1

Unit

EA

Pack Quantity

1

DVR60040400S
DVR60040400S
DVR60040400S

Information

The PowerLogic DVR series offer to industry a solution to regulate voltage and restore Sags. This equipment is part of the Dynamic Voltage Restorer solution, and do not work stand alone. The secondary unit brings additional capacity to the system power. Protection of sensitive loads in power distribution and transmission systems against voltage distortions. This secondary equipement combined with the main apparatus contribute to the -40 % sags correction at 400 VAC, for a system power of 600 kVA. Enclosure dimensions are 2152 mm in height, 1214 mm in width and 750 mm in depth, and a total weight of 1250 kg. The device passed the following tests: SEMI F47 (US) / IEC 61000-4-34 for sags performances, and received CE, Ctick and EAC certifications. The enclosures is floor standing, equiped with hinged doors locked by a special opening tool. Include a forced ventillation to cool the inverter and the transformer. The design of the equipement allows connection to Source and Loads from the top or bottom, but to DVR input and output only from the bottom. This asset is compatible with EcoStruxure Power Advisor and EcoStruxure Asset Advisor, and could be supported by a service plan. The PowerLogic DVR is designed to reduce voltage sags on power lines that cater to sensitive commercial and industrial equipments.

Technical Specifications

Product or component type

Voltage module

Network type

3P 3P + N

Network rated voltage

400 V AC

Network frequency

50/60 Hz +/- 10 %

[THDU] total harmonic distorsion

0…5 % (nominal) 5…8 % (maximum): output voltage regulated at +/- 1 % 8…10 % (short time): output voltage regulated at +/- 3 % 10 % (limit)

Sag correction capability

For 3 phases 40 % for 30 s, accuracy +/- 1 %

Sag correction response

3 ms

Ride-through time

40 ms

Output voltage accuracy

+/- 1 % typical

Admitted output load

Up to 100% in variation Up to 100% in unbalance Inverter overload 110 %, 30 s Inverter overload 150 %, 1 s

Efficiency

at global efficiency load factor (98 %) Linear load at at nominal power load factor ,PF 0.8 (97.7 %) Linear load at at nominal power load factor ,PF 1 (98.1 %) Non-linear load at at nominal power load factor (97.4 %)

Continuous regulation range

-20…20 %

Power capacity

600 kVA

Overload withstand

2 In, 60 s 5 In, 10 s 30 In, 200 ms 30 In, if overload is exceeded equipment integrity is not guaranteed, 200 ms

Mean time to repair

2 h

enclosure mounting

Floor-standing

Heat dissipation

Secondary function

Electromagnetic compatibility

Voltage dips and interruptions immunity test conforming to IEC 61000-4-34 Immunity for industrial environments conforming to IEC 61000-6-2 Emission standard for industrial environments conforming to IEC 61000-6-4

accessibility for operation

Front

Location of connection

Bottom

Type of cooling

Forced cooling

Noise level

75 dB

Material

Cold-rolled steel Hot-rolled steel

Surface finish

Polyester powder

Enclosure degree of protection

IP20

Overvoltage category

III

Pollution degree

2

Operating altitude

<= 1000 m without derating

Ambient air temperature for operation

0…40 °C

Relative humidity

0…95 % non-condensing

Standards

IEC 62477-1 SEMI F47 ISO 14001 ISO 9001

product certifications

CE EAC C-Tick

Ambient air temperature for storage

-15…45 °C

Net weight

1250 kg

height

2152 mm

Width

1214 mm

Colour

Light grey (RAL 7035)

Depth

750 mm

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

236.0 cm

Package 1 Width

84.5 cm

Package 1 Length

132.0 cm

Package 1 Weight

1425.0 kg

Warranty

18 months

Document Links

Datasheet