Trade Price
£5,511.66
Per
1
Unit
EACH
Pack Quantity
1
Air/water heat exchanger in the bayed enclosure system VX25. To fit 600 or 800 mm deep, 2,000 mm high VX25 enclosures. Air outlet either with 5 kW on each side or 10 kW on one side only. Flexible options for water connection on the top or bottom of the unit. Air/water heat exchanger in the bayed enclosure system VX25. To fit 600 or 800 mm deep and 2,000 mm high VX25 enclosures. Air outlet either with 5 kW on each side or 10 kW on one side only. Flexible options for water connection on the top or bottom of the unit. SK Liquid cooling package, air/water heat exchanger in the bayed enclosure system VX25, 9.5 kW, 230 V, 1~, 50/60 Hz, water-carrying parts: copper/brass, WHD: 300 x 2000 x 800 mm
Article number:
SK 3378.380
Design
Water-carrying parts, copper/brass (Cu/CuZn)
Colour
RAL 7035
Supply includes
Cooling unit ready for connection, wired to terminal strip
Front door with display
Rear panel
Multilingual documentation
Total cooling output
L 35 W 10 at 2000 l/h: 9.5 kW
Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Power consumption Pel
At 50 Hz: 350 W
At 60 Hz: 350 W
Rated current max.
At 50 Hz: 2.65 A
At 60 Hz: 2.62 A
Permissible operating pressure (p. max.)
1 ‐ 6 bar
Type of electrical connection
Connection clamp
Duty cycle
100 %
Cooling medium
Water (see Internet for specifications)
Water inlet temperature
7 °C...30 °C
Water connections
G ¾" internal thread
Temperature control
e-Comfort controller (factory setting +35 °C)
Operating temperature range
5 °C...70 °C
Note
Bayable by screw-fastening at the sides
Dimensions
Width: 300 mm
Height: 2,000 mm
Depth: 800 mm
Noise level
60 dB(A)
Pre-fuse
Miniature circuit-breaker/fuse: 4 A
Setting range
20 °C...55 °C
Protection category to IEC 60 529
IP 55
Packs of
1 pc(s).
Weight/pack
115 kg
Customs tariff number
84158200
EAN
4028177958272
ETIM 7.0
EC002515
ECLASS 8.0
27180712
Datasheet