Trade Price
£7,057.08
Per
1
Unit
EACH
Pack Quantity
1
Compact fire alarm and active extinguisher system with smoke extraction system, built into one height unit for use in security safes and closed server racks. The active extinguisher system includes the smoke extraction system and the extinguisher unit. The smoke extraction system is identical to the smoke extraction system in the EFD III. The extinguishing process begins automatically when a main alarm is activated. For the extinguishing process, the tank is pressurised via a propellant cartridge. The extinguisher gas Novec™ 1230 evaporates at the extinguisher nozzle and is distributed in the server enclosure. DET-AC III Master, fire alarm and extinguisher system, active smoke extraction system, early fire detection, automatic extinguishing.
Article number:
DK 7338.121
Benefits
Early fire detection
Technical specifications
Extinguisher is emitted via a propellant cartridge, with integral electrical activation unit
Material
Sheet steel
Colour
Enclosure: RAL 7035
Front: RAL 9005
Extinguisher gas
Type: Novec™ 1230
Fill volume: 1.8 l
Tank
Material: Aluminium
Volume: 2 l
Interfaces
4 x/3 x relay outputs for alarms and faults (terminals/RJ12 jacks)
Uninterruptible mains electricity operation
approx. 4 h
Note
This system is designed solely for use in closed, non-accessible enclosure systems with a maximum volume of 2.8 m³.
Display
Plain-language display with 6 LEDs
Sensors
Optical smoke detector (sensitivity: approx. 3.5%/m light obscuration)
Dimensions
Width: 482.6 mm
Height: 44 mm
Depth: 660 mm
Operating temperature range
10 °C...40 °C
Storage temperature range
-20 °C...65 °C
Storage temperature range of batteries
-15 °C...40 °C
Relative humidity (non-condensing)
96 %
Rated operating voltage
100 V - 240 V, 1~, 50 Hz/60 Hz
Air flow monitoring
approx. ±10% of total airflow
Packs of
1 pc(s).
Weight/pack
21.5 kg
Customs tariff number
84248970
EAN
4028177699311
ETIM 7.0
EC002685
ECLASS 8.0
40040104