Trade Price
£11,854.70
Per
1
Unit
EACH
Pack Quantity
1
Bayed climate control designed for siting within a bayed enclosure suite. The hot air is extracted at the rear of the unit, cooled and then expelled forwards to the cold aisle. SK LCP Inline CW/glycol, 28 kW, RAL 7035, WHD: 300 x 2000 x 1200 mm
Article number:
SK 3313.550
Design
Suite cooling
Benefits
Maximum energy efficiency due to EC fan technology and IT-based control
Function principle
The hot air is drawn in from the room or hot aisle at the rear of the device and expelled at the front into the cold aisle after cooling. With this product, a raised floor is not necessary.
Material
Sheet steel, spray-finished
Colour
RAL 7035
Options
Direct connection of additional CMC III sensors is supported
Racks 2200 mm high
Monitoring
Monitoring of all system-relevant parameters such as server air intake temperature, server waste air temperature, water inlet/return temperature, water flow, cooling output, fan speed, leakage
Total cooling output/Number of fan modules
20 kW/2
31 kW/3
35 kW/4
Air throughput (unimpeded air flow)
Air throughput at 50 Hz: 5,000 m³/h
Number of fans
2
Dimensions
Width: 300 mm
Height: 2,000 mm
Depth: 1,200 mm
To fit enclosure type
VX IT
Installation in bayed enclosure suite
Flush
Rated operating voltage
230 V, 1~, 50 Hz/60 Hz
Max. cooling output
28 kW
Type of electrical connection
Connector
Duty cycle
100 %
Cooling medium
Water/glycol
EC fan
Yes
Fans may be exchanged with the system operational
Yes
Temperature control
Linear fan control
Water connections
DN 40 (G 1½" external thread)
Permissible operating pressure (p. max.)
10 bar
Water inlet temperature
15 °C
Protection category to IEC 60 529
IP 20
Optimized condensate management even at low water flow temperatures
Yes
Packs of
1 pc(s).
Weight/pack
280 kg
Customs tariff number
84158200
EAN
4028177953932
ETIM 7.0
EC002515
ECLASS 8.0
27180712
Datasheet