Trade Price
£15,140.68
Per
1
Unit
EACH
Pack Quantity
1
Ideal for cooling of small and medium-sized IT applications. LCP Inline DX, 12 kW, flush, RAL 7035, WHD: 300 x 2000 x 1200 mm, 380 – 480 V/3~/50 – 60 Hz
Article number:
SK 3313.440
Design
Suite cooling
Benefits
Maximum energy efficiency due to EC fan technology and IT-based control
Applications
Ideal for IT cooling of small and medium-sized locations
Function principle
The LCP is designed for siting within a bayed enclosure suite. Hot air is drawn in from the aisle at the rear of the device, cooled by the high-capacity compact impellers, and blown back into the room or cold aisle after cooling.
Material
Sheet steel, spray-finished
Colour
RAL 7035
Options
Humidifier
Dehumidification and reheater
Condensate drain pump
Low-temperature/high-temperature condenser (-40 °C/+53 °C)
Monitoring
Direct connection of the unit via SNMP over Ethernet
Note
Variant with UL approval available on request
Total cooling output to DIN EN 14511
Useful cooling output L22 L35: 12 kW
Useful cooling output L22 L45: 10 kW
Modulation range
3 ‐ 12 kW
Total cooling output/Number of fan modules
12 kW/4
Air throughput (unimpeded air flow)
Air throughput at 50 Hz: 4,800 m³/h
Dimensions
Width: 300 mm
Height: 2,000 mm
Depth: 1,200 mm
To fit enclosure type
VX IT
Installation in bayed enclosure suite
Flush
Rated operating voltage
380 V - 480 V, 3~, 50 Hz/60 Hz
Rated current max.
At 50 Hz: 7.5 A
Max. cooling output
12 kW
Type of electrical connection
Connection clamp
Duty cycle
100 %
Cooling medium
Refrigerant
EC fan
Yes
SNMP card
Yes
Fans may be exchanged with the system operational
Yes
Temperature control
Linear fan control
Pre-fuse
Miniature circuit-breaker/fuse: 20 A
Storage temperature range
-20 °C...50 °C
Operating temperature range
5 °C...35 °C
Noise level
At 50 Hz: 69 dB(A)
Protection category to IEC 60 529
IP 20
Packs of
1 pc(s).
Weight/pack
201 kg
Customs tariff number
84195080
EAN
4028177953864
ETIM 7.0
EC002515
ECLASS 8.0
27180712