Trade Price
£5,869.14
Per
1
Unit
EACH
Pack Quantity
1
Energy-efficient Blue e+ wall-mounted cooling units in output categories 1600 W to 5800 W. Average energy savings of 75% can be achieved with speed-regulated components and heat pipe technology. Available in sheet steel and stainless steel versions. For mounting the roof-mounted unit. The cut-out in the door is arranged so that the roof-mounted cooling unit is positioned centrally on the door. SK cooling unit Blue e+, wall-mounted, 5.8 kW, 380-480 V, 3~, 50-60 Hz, Sheet steel, WHD: 450 x 1600 x 393 mm
Article number:
SK 3189.940
Benefits
Average 75% energy savings thanks to speed-regulated components and heat pipe technology
Material
Sheet steel
Colour
RAL 7035
Supply includes
Condenser with hydrophobic RiNano coating
Integral electric condensate evaporation
Assembly parts
Fully wired ready for connection (plug-in terminal strip)
Options
For remote monitoring and networking of cooling units and chillers in the Blue e+ generation, please use the IoT interface (Model No. 3124.300). Increase machine availability and process reliability with remote monitoring of device data, statuses and system messages.
Total cooling output to DIN EN 14511
Cooling output L35 L35/50 Hz: 5.8 kW
Cooling output L35 L35/60 Hz: 5.8 kW
Cooling output L35 L50/50 Hz: 4.2 kW
Cooling output L35 L50/60 Hz: 4.2 kW
Rated operating voltage
380 V - 480 V, 3~, 50 Hz/60 Hz
Note
Please observe the mounting instructions.
Note on Model No.
Tolerance: 380 V -10% (342 V) and 480 V +5% (509 V)
Rated power input
2.2 kW
Air throughput (unimpeded air flow)
External circuit: 2,300 m³/h
Internal circuit: 2,300 m³/h
Energy efficiency ratio (EER) 50/60 Hz L35 L35
Refrigeration factor L35 L35 (EER) 50 Hz: 2.64
Refrigeration factor L35 L35 (EER) 60 Hz: 2.64
Seasonal energy efficiency ratio (SEER) 50/60 Hz
6.2
Design
wall-mounted
Dimensions
Width: 450 mm
Height: 1,600 mm
Depth: 393 mm
Required mounting cut-out
Cut-out width: 433 mm
Cut-out height: 1,579 mm
Protection category to IEC 60 529
Internal circuit IP 55
Protection category NEMA
UL Type 3R/12
Refrigerant/cooling medium
Refrigerant: R134a
Quantity: 1.75 kg
Global Warming Potential (GWP): 1,430
CO₂ equivalent (CO₂e): 2.5 t
Temperature control
e+ controller (factory setting +35 °C)
Operating temperature range
-20 °C...60 °C
Storage temperature range
-40 °C...70 °C
Operating temperature range of refrigerant circuit (active)
3 °C...60 °C
Heat pipe operating temperature range
-20 °C...45 °C
Setting range
20 °C...50 °C
Power consumption Pel
Power consumption L35 L35/50 Hz: 2.2 kW
Power consumption L35 L35/60 Hz: 2.2 kW
Power consumption L35 L50/50 Hz: 2.2 kW
Power consumption L35 L50/60 Hz: 2.2 kW
Permissible operating pressure (p. max.)
24 bar
Packs of
1 pc(s).
Weight/pack
72.4 kg
Customs tariff number
84158200