Trade Price
£1,541.00
Per
1
Unit
EACH
Pack Quantity
1
circuit breaker 3VA2 IEC frame 250 breaking capacity class H Icu=85kA @ 415V 3-pole, line protection ETU860, LSIG, In=250A overload protection Ir=100A...250A short-circuit protection Isd=0.6..10x In, Ii=1.5..10x In N conductor protection optionally with external current transformer, up to 160% gr.-fault prot., can be sw. off Ig=0.2...1 x In, tg=0.05-0.8s nut keeper kit circuit breaker 3VA2 IEC frame 250 breaking capacity class H SHUNT TRIP LEFT 208-277 V AC 50/60 HZ 220-250 V DC ACCESSORY
Article Number
3VA2225-6KQ32-0KA0
Product family
Ordering Data Overview
Product Lifecycle (PLM)
PM300:Active Product
Price Group
12P
Surcharge for Raw Material
see also metal factor (further details are available on the help page)
Metal Factor
LOA-----
Export Control Regulations
AL : N / ECCN : EAR99
Standard lead time ex-works
5 Day(s)
Net Weight (kg)
2,582 Kg
Packaging Dimension
134,00 x 200,00 x 145,00
Package size unit of measure
MM
Quantity Unit
1 Piece
Packaging Quantity
1
EAN
4042949331100
UPC
Not available
Commodity Code
85362090
LKZ_FDB/ CatalogID
LV10.1
Product Group
5374
Group Code
P360
Country of origin
Czech Republic
Compliance with the substance restrictions according to RoHS directive
Since: 06.03.2020
Product class
C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit.
WEEE (2012/19/EU) Take-Back Obligation
Yes
Datasheet