Trade Price
£75.61
Per
1
Unit
EA
Pack Quantity
6
Neutral position
without neutral
Number of protected poles
2
Number of poles
2 P
Type of pole
2 P
Concurrently switching N-neutral
No
Number of modules
2
Top connection alignement for modular devices
Aligned terminal
Bottom connection alignement for modular devices
Aligned terminal
Rated short circuit breaking capacity Icn AC according IEC60898-1
10 kA
Rated operational voltage Ue
415 V
Type of supply voltage
AC
Rated insulation voltage
500 V
Max operating voltage
440 V
Rated impulse withstand voltage
6000 V
Minimum threshold voltage (Ue min)
12 V
Rated current
2 A
Rated service breaking capacity Ics AC according IEC 60898-1
7.5 kA
min/maxi threshold value of the AC thermal operation
1.13 / 1.45 In
Magnetic regulating currrent
10 / 14.4 In
min/maxi threshold value of the DC magnetic operation
15 / 30 In
min/maxi threshold value of the DC thermal operation
1.13 / 1.45 In
Rating current -10°C according to IEC 60947
2.97 A
Rating current -15°C according to IEC 60947
3.03 A
Rating current -20°C according to IEC 60947
3.1 A
Rating current -25°C according to IEC 60947
3.16 A
Rating current -5°C according to IEC 60947
2.9 A
Rating current 0°C according to IEC 60947
2.83 A
Rating current 10°C according to IEC 60947
2.68 A
Rating current 150°C according to IEC 60947
2.61 A
Rating current 20°C according to IEC 60947
2.53 A
Rating current 25°C according to IEC 60947
2.45 A
Rating current 30°C according to IEC 60947
2.37 A
Rating current 35°C according to IEC 60947
2.28 A
Rating current 40°C according to IEC 60947
2.19 A
Rating current 45°C according to IEC 60947
2.1 A
Rating current 5°C according to IEC 60947
2.76 A
Rating current 50°C according to IEC 60947
2 A
Rating current 55°C according to IEC 60947
1.9 A
Rating current 60°C according to IEC 60947
1.79 A
Rating current 65°C according to IEC 60947
1.67 A
Rating current 70°C according to IEC 60947
1.55 A
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1
10 kA
Rated short circuit breaking capacity Icn under 400V AC according IEC60898-1
10 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
30 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
30 kA
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
15 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
15 kA
Rated short circuit breaking capacity Icn under 240V AC according IEC 60898-1
10 kA
Rated short circuit breaking capacity Icn under 415V AC according IEC 60898-1
10 kA
Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2
30 kA
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2
15 kA
Rating current -25°C
2.67 A
Rating current -20°C
2.62 A
Rating current -15°C
2.56 A
Rating current -10°C
2.51 A
Rating current -5°C
2.45 A
Rating current 0°C
2.39 A
Rating current 5°C
2.33 A
Rating current 10°C
2.27 A
Rating current 25°C
2.07 A
Rating current 30°C
2 A
Rating current 35°C
1.93 A
Rating current 40°C
1.85 A
Rating current 45°C
1.77 A
Rating current 50°C
1.69 A
Rating current 55°C
1.6 A
Rating current 60°C
1.51 A
Rating current 65°C
1.41 A
Rating current 70°C
1.31 A
Correction factor of rating current for 2 devices placed side-by-side
1
Correction factor of rating current for 3 devices placed side-by-side
0.95
Correction factor of rating current for 4 and 5 devices placed side-by-side
0.9
Correction factor of rating current for 6 devices placed side-by-side
0.85
Correction factor of magnetic tripping with 100 Hz
1.1
Correction factor of magnetic tripping with 200 Hz
1.2
Correction factor of magnetic tripping with 400 Hz
1.5
Correction factor of magnetic tripping with 60 Hz
1.1
Depth of installed product
70 mm
Height of installed product
83 mm
Width of installed product
35 mm
Frequency
50 to 60 Hz
Maximum power loss per pole according to the product standard
3 W
Total power loss under IN
4.1 W
Power loss per pole at In
2.1 W
Electric endurance in number of cycles
4000
Number of mechanical operations
20000
Type of top connection for modular devices
with screw
Tightening torque
2,8Nm
Type of top rail clip for modular devices
NA
Type of bottom rail clip for modular devices
plastic
Type of Bottom Connection for modular devices
BIconnect
Top removability for modular devices
Yes
Bottom removability for modular devices
Yes
Suitable for flush-mounting
Yes
Connection cross-section at output with screw, for flexible conductor
1 / 25 mm²
Connection cross-section at output with screw, for massive conductor
1 / 35 mm²
Connection cross-section for rigid conductor, upstream terminals with screws
1 / 35 mm²
Connection cross-section of the access with screws, with flexible conductor
1 / 25 mm²
Downstream cage clamp delivery status
opened
Upstream cage clamp delivery status
opened
Can be accessorized
Yes
Standard text
EN 60898-1
European directive WEEE
concerned
Protection index IP
IP20
Operating temperature
-25…70 °C
Altitude
2000 m
Storage/transport temperature
-25…80 °C
Temperature of calibration
30 °C