HMW400NR

MCCB h3+ P630 Energy 3x400A 50kA

Trade Price

£1,526.46

Per

1

Unit

EA

Pack Quantity

1

HMW400NR

Technical Specifications

Neutral position

without neutral

Number of protected poles

3

Number of poles

3 P

Fixing mode

fixing plate

Type of case

Fixed built-in

Complete device with protection unit

Yes

Version as main switch

Yes

Version as emergency stop installation

No

Version as safety switch

No

Version as maintenance-/service switch

Yes

Trip Unit

ENERGY

Integrated earth fault protection

No

Motor drive integrated

No

Rated operational voltage Ue

220 / 690 V

Type of supply voltage

AC

Frequency

50 to 60 Hz

Rated insulation voltage

800 V

Rated impulse withstand voltage

8 kV

With under voltage release

No

Rated current

400 A

Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2

12 kA

Rating current 10°C according to IEC 60947

400 A

Rating current 150°C according to IEC 60947

400 A

Rating current 20°C according to IEC 60947

400 A

Rating current 25°C according to IEC 60947

400 A

Rating current 30°C according to IEC 60947

400 A

Rating current 35°C according to IEC 60947

400 A

Rating current 40°C according to IEC 60947

400 A

Rating current 45°C according to IEC 60947

400 A

Rating current 50°C according to IEC 60947

400 A

Rating current 55°C according to IEC 60947

400 A

Rating current 60°C according to IEC 60947

400 A

Rating current 65°C according to IEC 60947

396 A

Rating current 70°C according to IEC 60947

360 A

Rated service breaking capacity Ics under 660V AC according IEC 60947-2

12 kA

Breaking capacity on 1 pole for IT 230V NF 60947-2

10 kA

Breaking capacity on 1 pole for IT 400V NF 60947-2

10 kA

Breaking capacity on 1 pole for IT 415V NF 60947-2

10 kA

Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2

85 kA

Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2

85 kA

Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2

50 kA

Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2

50 kA

Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2

85 kA

Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2

50 kA

Rated ultimate short-circuit breaking capacity Icu under 660V AC IEC 60947-2

12 kA

Depth of installed product

150 mm

Height of installed product

260 mm

Width of installed product

140 mm

Total power loss under IN

90 W

Power loss per pole at In

30 W

Time of response when opening

10 ms

DIN rail mounting with optional adaptator

No

Suitable for front mounting

No

Suitable for ground mounting

Yes

Type of connection

Terminal

Cable Material

Cu

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Motor drive optional

Yes

Can be accessorized

Yes

European directive WEEE

concerned

Protection index IP

IP4X

Degree of pollution according to IEC 60664 / IEC 60947-2

3

Altitude

2000 m

Document Links

Datasheet