Trade Price
£108.71
Per
1
Unit
EACH
Pack Quantity
1
Eaton Moeller series NZM - Molded Case Circuit Breaker. Shunt release, 110-130VAC/DC, 2/3
Product Length/Depth
42 mm
Product Height
90 mm
Product Width
30 mm
Product Weight
0.095 kg
Warranty
Eaton Selling Policy 25-000, one (1) year from the date of installation of the Product or eighteen (18) months from the date of shipment of the Product, whichever occurs first.
Compliances
UL/CSA
IEC
RoHS conform
Certifications
UL489
UL (File No. E140305)
CSA (File No. 22086)
CE marking
UL listed
CSA-C22.2 No. 5-09
CSA certified
IEC60947
CSA (Class No. 1437-01)
UL (Category Control Number DIHS)
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Rated control supply voltage (Us) at AC, 50 Hz - min
110 V
10.4 Clearances and creepage distances
Meets the product standard's requirements.
Minimum command time - min
10 ms
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Rated control supply voltage (Us) at DC - min
110 V
Rated control supply voltage (Us) at AC, 50 Hz - max
130 V
Frequency rating
50 Hz / 60 Hz / 200 Hz / 400 Hz, DC (shunt release)
10.8 Connections for external conductors
Is the panel builder's responsibility.
Minimum command time - max
15 ms
Special features
Switches are tripped by a voltage pulse or by the application of uninterrupted voltage.
If the shunt trip is live, contact with the circuit breaker’s primary contacts is prevented when switched on.
Shunt releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
Voltage rating at AC (x Us) - min
.7
Rated control supply voltage (Us) at DC - max
130 V
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Rated control supply voltage
110 - 130 V AC/DC
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Used with
NZM2(-4), N(S)2(-4)
NZM3(-4), N(S)3(-4)
Electric connection type
Screw connection
Voltage rating at AC (x Us) - max
1.1
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Number of contacts (normally closed contacts)
0
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Voltage type
AC/DC
Frame
NZM2/3
Reaction time
20 ms
Suitable for
Off-load switch
Pick-up power consumption (shunt release)
2.5 VA/W
Rated control voltage (relay contacts)
110 V AC
130 V DC
110 V DC
130 V AC
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
Time on duty - max
∞
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
Connection type
With bolt connection
Voltage rating
0.7 - 1.1 x Us
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Undelayed short-circuit release - min
0 A
Rated control supply voltage (Us) at AC, 60 Hz - min
110 V
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Terminal capacity (solid/flexible conductor)
0.75 mm² - 2.5 mm² (1x) for undervoltage releases, off-delayed with ferrule
0.75 mm² - 2.5 mm² (2x) for undervoltage releases, off-delayed with ferrule
18 - 14 AWG (2x) for undervoltage releases, off-delayed
0.75 mm² - 2.5 mm² (1x) at shunt release with ferrule
0.75 mm² - 2.5 mm² (2x) at shunt release with ferrule
18 - 14 AWG (1x) for undervoltage releases, off-delayed
18 - 14 AWG (1x) at shunt release
18 - 14 AWG (2x) at shunt release
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Type
Accessory
Shunt release
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Rated control supply voltage (Us) at AC, 60 Hz - max
130 V
Number of contacts (normally open contacts)
0
Undelayed short-circuit release - max
0 A
Number of contacts (change-over contacts)
0
Datasheet