Trade Price
£303.67
Per
1
Unit
EA
Pack Quantity
1
TeSys enclosed starter with switch disconnector, 3 poles, Ithe 140A 690V, for main and emergency stop switching in motor applications up to 45kW@400V AC-23. Enclosure providing IP65 protection, fitted with a red rotary handle and yellow front plate, padlockable (padlocks not included). It includes a 3-pole Vario switch body V6 with 1 possible add-on module attachments. Surface mounting enclosure with screw fixing, 2 knock-outs for cable glands on top and bottom, sealable cover. It conforms to IEC 60204 and IEC 60947-4-1, Green Premium compliant (RoHS/REACh).
Range
TeSys
Product name
TeSys VARIO
Device short name
VCF
Product or component type
Enclosed emergency stop switch disconnector
Performance level
High performance
Poles description
3P
Control type
Rotary handle
Type of operator
Long handle
handle colour
Red
Handle front plate colour
Yellow
Rotary handle padlocking
1 to 3 padlocks 4…8 mm
Marking
0 - 1
[Ue] rated operational voltage
690 V AC
[Uimp] rated impulse withstand voltage
8 kV
[Ithe] conventional enclosed thermal current
140 A
[Ie] rated operational current
83 A (AC-23A) at 400 V
Rated operational power in W
45 kW at 400 V (AC-23) 37 kW at 400 V (AC-3)
Intermittent duty class
30
Making capacity ( I rms)
1750 A at 400 V AC-21A 1750 A at 400 V AC-22A 1750 A at 400 V AC-23A
[Icm] rated short-circuit making capacity
2.8 kA at 400 V at Ipeak
[Icw] rated short-time withstand Rms current
2100 A at 400 V duration: 1 s
Rated conditional short-circuit current
10 kA at 400 V - associated fuse 200 A aM 10 kA at 400 V - associated fuse 200 A gG
Breaking capacity
1400 A at 400 V (AC-21A) 1400 A at 400 V (AC-22A) 1400 A at 400 V (AC-23A)
Mechanical durability
30000 cycles
Electrical durability
30000 cycles AC-21 30000 cycles DC-1...5
Environmental characteristic
Standard environment
Suitability for isolation
Yes
Connections - terminals
Screw clamp terminals70 mm² - flexible - with cable end Screw clamp terminals95 mm² - solid
Tightening torque
22.6 N.m - on screw clamp terminals
Fire resistance
960 °C conforming to IEC 60595-2-1
handle front plate dimension
90 x 90 mm
height
291 mm
Width
241 mm
Depth
191 mm
Net weight
2.19 kg
standards
IEC 60204 IEC 60947-4-1
Protective treatment
TC
IP degree of protection
IP65 conforming to IEC 60529
Mechanical robustness
Vibrations 10...150 Hz (1 gn) conforming to IEC 60068-2-6 Shocks 11 ms (30 Gn) conforming to IEC 60068-2-27
Ambient air temperature for operation
-20…50 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
30.000 cm
Package 1 Width
20.500 cm
Package 1 Length
30.000 cm
Package 1 Weight
2.908 kg
Unit Type of Package 2
S04
Number of Units in Package 2
2
Package 2 Height
30.000 cm
Package 2 Width
40.000 cm
Package 2 Length
60.000 cm
Package 2 Weight
6.577 kg
Unit Type of Package 3
P06
Number of Units in Package 3
8
Package 3 Height
75.000 cm
Package 3 Width
60.000 cm
Package 3 Length
80.000 cm
Package 3 Weight
38.788 kg
Warranty
18 months
Datasheet