LR9D5567

OVERLOAD RELAY

Trade Price

£526.51

Per

1

Unit

EA

Pack Quantity

1

LR9D5567

Information

TeSys LR9D electronic overload relay, 100A/1000V, thermal setting range 60-100A, tripping class 20, for protection of 3-phase motors 37-45kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, buttons for test, stop and reset, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by bolt terminals for bars or cables with lugs, it connects directly to the bottom terminals of 3-pole contactors LC1D115, D150. Mounting on DIN rail or screw fixing, separated from contactor, can be done without accessories. Multi-standards certified (IEC, UL, CSA, CCC, Marine), Green Premium compliant (RoHs/Reach).

Technical Specifications

Range

TeSys

Product name

TeSys LRD TeSys Deca

Product or component type

Electronic thermal overload relay

Device short name

LR9D

Relay application

Motor protection

Product compatibility

LC1D150 NSX circuit breaker LC1D115

Network type

AC

Thermal overload class

Class 20 conforming to IEC 60947-4-1

Signalling function

Alarm

Thermal protection adjustment range

60…100 A

[Ui] rated insulation voltage

Power circuit: 1000 V conforming to IEC 60947-4-1 Power circuit: 600 V conforming to CSA Power circuit: 600 V conforming to UL

Network frequency

50...60 Hz

[Us] rated supply voltage

24 V DC

Supply voltage limits

17…32 V

Mounting support

Under contactor Rail

Tripping threshold

1.05 +/- 0.06 In alarm conforming to IEC 60947-4-1 1.12 +/- 0.06 In de-energisation conforming to IEC 60947-4-1

Auxiliary contact composition

1 NO + 1 NC

[Ith] conventional free air thermal current

5 A for signalling circuit

[Ue] rated operational voltage

690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1

Associated fuse rating

4 A gG for signalling circuit 4 A BS for signalling circuit

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-1

Phase failure sensitivity

Tripping in 4 s +/- 20 % conforming to IEC 60947-4-1

Control type

Red push-button: stop Blue push-button: reset

Temperature compensation

-20…60 °C

Switching capacity in mA

0...150 mA

Maximum voltage drop

<2.5 V closed state

Connections - terminals

Power circuit: bars Control circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 0.5…1.5 mm² flexible without cable end Alarm circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end

Tightening torque

Alarm circuit: 0.45 N.m - on screw clamp terminals Power circuit: 18 N.m - on bars M8 Control circuit: 1.2 N.m - on screw clamp terminals

height

118 mm

Width

115 mm

Depth

125 mm

Net weight

0.885 kg

Climatic withstand

conforming to IACS E10

IP degree of protection

IP20 conforming to IEC 60529

Ambient air temperature for operation

-20…60 °C without derating conforming to IEC 60947-4-1

Ambient air temperature for storage

-60…70 °C

Operating altitude

<= 2000 m without derating

Mechanical robustness

Vibrations: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7

Dielectric strength

1.89 kV at 50 Hz conforming to IEC 60947-1

standards

EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4 GB/T 14048.5

product certifications

UL CSA CCC UKCA

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

15.0 cm

Package 1 Width

15.5 cm

Package 1 Length

13.0 cm

Package 1 Weight

935.0 g

Unit Type of Package 2

S04

Number of Units in Package 2

12

Package 2 Height

30.0 cm

Package 2 Width

40.0 cm

Package 2 Length

60.0 cm

Package 2 Weight

12.005 kg

Warranty

18 months

Document Links

Datasheet

Technical Data