TeSys LR9D electronic overload relay, 100A/1000V, thermal setting range 60-100A, tripping class 10, for protection of 3-phase motors 37-45kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, buttons for test, stop and reset, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by bolt terminals for bars or cables with lugs, it connects directly to the bottom terminals of 3-pole contactors LC1D115, D150. Mounting on DIN rail or screw fixing, separated from contactor, can be done without accessories. Multi-standards certified (IEC, UL, CSA, CCC, Marine), Green Premium compliant (RoHs/Reach).
Range
TeSys
Product name
TeSys LRD TeSys Deca
Product or component type
Electronic thermal overload relay
Device short name
LR9D
Relay application
Motor protection
Product compatibility
LC1D115 LC1D150 NSX circuit breaker
Network type
AC
Thermal overload class
Class 10 conforming to IEC 60947-4-1
Signalling function
Alarm
Thermal protection adjustment range
60…100 A
[Ui] rated insulation voltage
Power circuit: 1000 V conforming to IEC 60947-4-1 Power circuit: 600 V conforming to CSA Power circuit: 600 V conforming to UL
Network frequency
50...60 Hz
[Us] rated supply voltage
24 V DC
Supply voltage limits
17…32 V
Mounting support
Under contactor Rail
Tripping threshold
1.05 +/- 0.06 In alarm conforming to IEC 60947-4-1 1.12 +/- 0.06 In de-energisation conforming to IEC 60947-4-1
Auxiliary contact composition
1 NO + 1 NC
[Ith] conventional free air thermal current
5 A for signalling circuit
[Ue] rated operational voltage
690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating
4 A gG for signalling circuit 4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-1
Phase failure sensitivity
Tripping in 4 s +/- 20 % conforming to IEC 60947-4-1
Control type
Red push-button: stop Blue push-button: reset
Temperature compensation
-20…60 °C
Switching capacity in mA
0...150 mA
Maximum voltage drop
<2.5 V closed state
Connections - terminals
Power circuit: bars Control circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 0.5…1.5 mm² flexible without cable end Alarm circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end
Tightening torque
Alarm circuit: 0.45 N.m - on screw clamp terminals Power circuit: 18 N.m - on bars M8 Control circuit: 1.2 N.m - on screw clamp terminals
height
118 mm
Width
115 mm
Depth
125 mm
Net weight
0.885 kg
Climatic withstand
conforming to IACS E10
IP degree of protection
IP20 conforming to IEC 60529
Ambient air temperature for operation
-20…60 °C without derating conforming to IEC 60947-4-1
Ambient air temperature for storage
-60…70 °C
Operating altitude
<= 2000 m without derating
Mechanical robustness
Vibrations: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7
Dielectric strength
1.89 kV at 50 Hz conforming to IEC 60947-1
standards
EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4 GB/T 14048.5
product certifications
UL CSA CCC UKCA
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
15.0 cm
Package 1 Width
16.0 cm
Package 1 Length
13.0 cm
Package 1 Weight
934.0 g
Unit Type of Package 2
S04
Number of Units in Package 2
12
Package 2 Height
30.0 cm
Package 2 Width
40.0 cm
Package 2 Length
60.0 cm
Package 2 Weight
11.978 kg
Warranty
18 months
Datasheet
Technical Data