Trade Price
£63.21
Per
1
Unit
EA
Pack Quantity
1
Range
TeSys
Product name
TeSys LRK
Product or component type
Non differential thermal overload relay
Device short name
LR7K
Relay application
Motor protection
Product compatibility
LP4K LP1K LC7K LC1K
Network type
AC DC
Thermal overload class
Class 10A conforming to IEC 60947-4-1
Thermal protection adjustment range
5.5…8 A
[Ui] rated insulation voltage
Power circuit: 690 V conforming to BS 4941 Power circuit: 690 V conforming to IEC 60947 Power circuit: 750 V conforming to VDE 0110 group C Power circuit: 600 V conforming to CSA C22.2 No 14
Network frequency
<= 400 Hz
Mounting support
Under contactor Plate, with specific accessories Rail, with specific accessories
Auxiliary contact composition
1 NO + 1 NC
[Ith] conventional free air thermal current
6 A for signalling circuit
[Ue] rated operational voltage
<= 690 V for power circuit 690 V AC AC-15 for signalling circuit 250 V DC DC-13 for signalling circuit
Associated fuse rating
6 A gG for signalling circuit conforming to VDE 0660 6 A gG for signalling circuit conforming to IEC 60947
[Uimp] rated impulse withstand voltage
6 kV
Power dissipation per pole
2 W
Local signalling
Trip indicator (yellow)
Control type
Red push-button: trip test function Blue push-button: stop and manual reset selector switch: manual or automatic reset
Connections - terminals
Screw clamp terminals 1 cable(s) 1.5…4 mm²solid Screw clamp terminals 2 cable(s) 1.5…4 mm²solid Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
Tightening torque
1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm 1.3 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
height
58 mm
Width
45 mm
Depth
65 mm
Net weight
0.145 kg
standards
VDE 0660 IEC 60947 NF C 63-650 BS 4941
product certifications
UL CSA UKCA
Protective treatment
TC conforming to IEC 60068 TC conforming to DIN 50016
IP degree of protection
IP2X conforming to IEC 60529
Ambient air temperature for operation
-20…55 °C without derating conforming to IEC 60947 -30…60 °C with derating conforming to IEC 60947
Ambient air temperature for storage
-40…70 °C
Operating altitude
2000 m without derating
Fire resistance
850 °C conforming to IEC 60695-2-1
Flame retardance
V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
Mechanical robustness
Shocks NO contact: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks NC contact: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations NO contact: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations NC contact: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
4.8 cm
Package 1 Width
7.2 cm
Package 1 Length
8.5 cm
Package 1 Weight
153.0 g
Unit Type of Package 2
S02
Number of Units in Package 2
41
Package 2 Height
15.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
6.628 kg
Warranty
18 months
Datasheet
Technical Data