LC2K0610E7

Rev cont-3NO 6A AC3 poles

Trade Price

£88.07

Per

1

Unit

EA

Pack Quantity

1

LC2K0610E7

Information

TeSys K reversing contactor, 3 poles (3NO), for motor control applications up to 6A/690V AC-3 (2.2kW@400V). It provides 48V 50/60Hz AC coils, 2NO built-in auxiliary contacts, connection by screw clamp terminals. For operating rates until 600 cycles/hour in AC-3 and environments until 50°C, it procures reliability and durability to standard applications. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys

Product name

TeSys K

Product or component type

Reversing contactor

Device short name

LC2K

Device application

Control

contactor application

Motor control

utilisation category

AC-3 AC-3e AC-4

Device presentation

Preassembled with reversing power busbar

Poles description

3P

power pole contact composition

3 NO

[Ue] rated operational voltage

Power circuit: 690 V AC 50/60 Hz Signalling circuit: <= 690 V AC 50/60 Hz

[Ie] rated operational current

6 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 6 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

Motor power kW

1.5 kW at 220...230 V AC 50/60 Hz 2.2 kW at 380...415 V AC 50/60 Hz 3 kW at 440/690 V AC 50/60 Hz

Control circuit type

AC at 50/60 Hz

[Uc] control circuit voltage

48 V AC 50/60 Hz

Auxiliary contact composition

1 NO

[Uimp] rated impulse withstand voltage

8 kV

Overvoltage category

III

[Ith] conventional free air thermal current

20 A (at 60 °C) for power circuit 10 A (at 50 °C) for signalling circuit

Irms rated making capacity

110 A AC for power circuit conforming to IEC 60947 110 A AC for signalling circuit conforming to IEC 60947

Rated breaking capacity

110 A at 220...230 V conforming to IEC 60947 110 A at 380...400 V conforming to IEC 60947 110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947

[Icw] rated short-time withstand current

90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit

Associated fuse rating

25 A gG at <= 440 V for power circuit 25 A aM for power circuit 10 A gG for signalling circuit conforming to IEC 60947 10 A gG for signalling circuit conforming to VDE 0660

Average impedance

3 mOhm - Ith 20 A 50 Hz for power circuit

[Ui] rated insulation voltage

Power circuit: 600 V conforming to UL 508 Power circuit: 690 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-5-1 Signalling circuit: 600 V conforming to UL 508 Power circuit: 600 V conforming to CSA C22.2 No 14 Signalling circuit: 600 V conforming to CSA C22.2 No 14

Electrical durability

1.3 Mcycles 6 A AC-3 at Ue <= 440 V 1.3 Mcycles 6 A AC-3e at Ue <= 440 V 0.05 Mcycles 36 A AC-4 at Ue <= 440 V

Interlocking type

Mechanical

mounting support

Rail Plate

standards

EN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1

product certifications

CB Scheme CCC UL CSA EAC CE UKCA

Connections - terminals

Screw clamp terminals 1 cable(s) 1.5…4 mm²solid Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1.5…4 mm²solid Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end

Tightening torque

0.8…1.3 N.m - on screw clamp terminals Philips No 2 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm 0.8…1.3 N.m - on screw clamp terminals pozidriv No 2

Operating time

10...20 ms coil energisation and NO closing 10...20 ms coil de-energisation and NO opening

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability

5 Mcycles

Maximum operating rate

3600 cyc/h

Control circuit voltage limits

Operational: 0.8...1.15 Uc (at <50 °C) Drop-out: 0.2...0.75 Uc (at <50 °C)

Inrush power in VA

30 VA (at 20 °C)

Hold-in power consumption in VA

4.5 VA (at 20 °C)

Heat dissipation

1.3 W

Auxiliary contacts type

type instantaneous 1 NO

Signalling circuit frequency

<= 400 Hz

Minimum switching current

5 mA for signalling circuit

Minimum switching voltage

17 V for signalling circuit

Non overlap distance

0.5 mm

Insulation resistance

> 10 MOhm for signalling circuit

IP degree of protection

IP20 conforming to VDE 0106

Protective treatment

TC conforming to IEC 60068 TC conforming to DIN 50016

Ambient air temperature for operation

-25…50 °C

Ambient air temperature for storage

-50…80 °C

Operating altitude

2000 m without derating

Flame retardance

V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102

Mechanical robustness

Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6

height

58 mm

Width

90 mm

Depth

57 mm

Net weight

0.39 kg

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

6.0 cm

Package 1 Width

6.5 cm

Package 1 Length

9.2 cm

Package 1 Weight

363.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

25

Package 2 Height

15.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

9.575 kg

Warranty

18 months

Document Links

Datasheet

Technical Data