LC1D95N7

CONT 95A 415V50/60Hz

Trade Price

£411.75

Per

1

Unit

EA

Pack Quantity

1

LC1D95N7

Technical Specifications

Range

TeSys

Range of product

TeSys Deca

Product or component type

Contactor

Device short name

LC1D

contactor application

Resistive load Motor control

utilisation category

AC-3 AC-3e AC-4 AC-1

Poles description

3P

[Ue] rated operational voltage

Power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current

95 A (at <60 °C) at <= 440 V AC-3 for power circuit 125 A (at <60 °C) at <= 690 V AC-1 for power circuit 95 A (at <60 °C) at <= 440 V AC-3e for power circuit

[Uc] control circuit voltage

415 V AC 50/60 Hz

Motor power kW

25 kW at 220...230 V AC 50 Hz (AC-3) 45 kW at 380...400 V AC 50 Hz (AC-3) 45 kW at 415...440 V AC 50 Hz (AC-3) 55 kW at 500 V AC 50 Hz (AC-3) 45 kW at 660...690 V AC 50 Hz (AC-3) 15 kW at 400 V AC 50 Hz (AC-4) 25 kW at 220...230 V AC 50 Hz (AC-3e) 45 kW at 380...400 V AC 50 Hz (AC-3e) 45 kW at 415...440 V AC 50 Hz (AC-3e) 55 kW at 500 V AC 50 Hz (AC-3e) 45 kW at 660...690 V AC 50 Hz (AC-3e)

Motor power hp

7.5 hp at 120 V AC 60 Hz for 1 phase motors 15 hp at 230/240 V AC 60 Hz for 1 phase motors 30 hp at 200/208 V AC 60 Hz for 3 phases motors 30 hp at 230/240 V AC 60 Hz for 3 phases motors 60 hp at 460/480 V AC 60 Hz for 3 phases motors 60 hp at 575/600 V AC 60 Hz for 3 phases motors

Compatibility code

LC1D

Pole contact composition

3 NO

Contact compatibility

M11

Protective cover

With

[Ith] conventional free air thermal current

10 A (at 60 °C) for signalling circuit 125 A (at 60 °C) for power circuit

Irms rated making capacity

1100 A at 440 V AC for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1

Rated breaking capacity

1100 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current

1100 A 40 °C - 1 s for power circuit 800 A 40 °C - 10 s for power circuit 400 A 40 °C - 1 min for power circuit 135 A 40 °C - 10 min for power circuit 140 A - 100 ms for signalling circuit 120 A - 500 ms for signalling circuit 100 A - 1 s for signalling circuit

Associated fuse rating

10 A gG for signalling circuit conforming to IEC 60947-5-1 200 A gG at <= 690 V coordination type 1 for power circuit 160 A gG at <= 690 V coordination type 2 for power circuit

Average impedance

0.8 mOhm - Ith 125 A 50 Hz for power circuit

Power dissipation per pole

12.5 W AC-1 7.2 W AC-3 7.2 W AC-3e

[Ui] rated insulation voltage

Power circuit: 1000 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified

Overvoltage category

III

Pollution degree

3

[Uimp] rated impulse withstand voltage

8 kV conforming to IEC 60947

Safety reliability level

B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability

4 Mcycles

Electrical durability

1.2 Mcycles 95 A AC-3 1.3 Mcycles 125 A AC-1 1.2 Mcycles 95 A AC-3e

Control circuit type

AC at 50/60 Hz

Coil technology

Without built-in suppressor module

Control circuit voltage limits

0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz 0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 1...1.1 Uc (55…70 °C):operational AC 50/60 Hz

Inrush power in VA

245 VA 60 Hz cos phi 0.75 (at 20 °C) 245 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA

26 VA 60 Hz cos phi 0.3 (at 20 °C) 26 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation

6…10 W at 50/60 Hz

Operating time

20...35 ms closing 6...20 ms opening

Maximum operating rate

3600 cyc/h 60 °C

Connections - terminals

Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end Power circuit: connector 1 4…50 mm² - cable stiffness: flexible without cable end Power circuit: connector 2 4…25 mm² - cable stiffness: flexible without cable end Power circuit: connector 1 4…50 mm² - cable stiffness: flexible with cable end Power circuit: connector 2 4…16 mm² - cable stiffness: flexible with cable end Power circuit: connector 1 4…50 mm² - cable stiffness: solid without cable end Power circuit: connector 2 4…25 mm² - cable stiffness: solid without cable end

Tightening torque

Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm Power circuit: 12 N.m - on connector hexagonal screw head 4 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Auxiliary contact composition

1 NO + 1 NC

Auxiliary contacts type

type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency

25...400 Hz

Minimum switching voltage

17 V for signalling circuit

Minimum switching current

5 mA for signalling circuit

Insulation resistance

> 10 MOhm for signalling circuit

Non-overlap time

1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact

mounting support

Rail Plate

Standards

EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4

product certifications

IECEE CB Scheme UL CSA CCC EAC LROS (Lloyds register of shipping) RINA BV DNV-GL

IP degree of protection

IP20 front face conforming to IEC 60529

Protective treatment

TH conforming to IEC 60068-2-30

Climatic withstand

conforming to IACS E10 exposure to damp heat

Permissible ambient air temperature around the device

-40…60 °C 60…70 °C with derating

Operating altitude

0...3000 m

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

Vibrations contactor open (2 Gn, 5...300 Hz) Shocks contactor open (8 Gn for 11 ms) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms)

height

127 mm

Width

85 mm

Depth

130 mm

Net weight

1.61 kg

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

14.224 cm

Package 1 Width

9.652 cm

Package 1 Length

13.208 cm

Package 1 Weight

1.565 kg

Warranty

18 months

Document Links

Datasheet

Technical Data